Low Voltage Cables
600 / 1000V 2-Core ~ 4-Core Mica Tape Fire Barrier,
XLPE Insulated, Unarmoured & Armoured
LSZH Sheathed, Fire Resistant Cable
APPLICATION |
This cable is designed for areas where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground tunnels, communications systems, sewage treatment plants, lifts, escalators, and high-rise buildings.
|
VOLTAGE RATING |
600/1000V
|
CONSTRUCTION |
Plain annealed copper, mica tape fire barrier, XLPE or XLEVA compound insulated, unarmoured or aluminum wires armoured, LSZH compound sheathed cable
|
INSULATION COLOUR |
|
SHEATH COLOUR |
Orange or as per order
|
SPECIFICATION |
BS7846, BS6387, SS299, IEC60331, IEC60332-1, IEC60332-3, IEC60754, IEC61034
|
- Detailed Specification
- Current Rating and Voltage Drop
2-CORE
| |||||||||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| ||||||||||||
Nominal Area
|
No./Dia of Strand
|
Dia. of Conductor
|
Thickness
|
Approx. Overall Diameter
|
Approx. Cable weight
|
Approx. Overall Diameter
|
Approx. Cable weight
| ||||||||
mm2
|
No./mm
|
mm
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||||||
1.5
|
7/0.53
|
1.59
|
0.7
|
12.2
|
150
|
15.3
|
390
| ||||||||
2.5
|
7/0.67
|
2.01
|
0.7
|
12.6
|
180
|
16.5
|
450
| ||||||||
4
|
7/0.85
|
2.55
|
0.7
|
14.7
|
250
|
17.6
|
525
| ||||||||
6
|
7/1.04
|
3.12
|
0.7
|
16.2
|
290
|
18.8
|
620
| ||||||||
10
|
7/1.35
|
4.05
|
0.7
|
17.1
|
450
|
21.0
|
800
| ||||||||
16
|
7/1.70
|
5.10
|
0.7
|
19.2
|
550
|
23.0
|
1100
| ||||||||
25
|
7/2.14
|
6.42
|
0.9
|
20.0
|
680
|
27.0
|
1480
| ||||||||
35
|
19/1.53
|
7.65
|
0.9
|
22.0
|
940
|
30.0
|
2000
| ||||||||
50
|
19/1.78
|
8.90
|
1.0
|
24.0
|
1250
|
33.0
|
2450
| ||||||||
70
|
19/2.14
|
10.70
|
1.1
|
27.0
|
1700
|
37.0
|
3200
|
3-CORE
| |||||||||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| ||||||||||||
Nominal Area
|
No./Dia of Strand
|
Dia. of Conductor
|
Thickness
|
Approx. Overall Diameter
|
Approx. Cable weight
|
Approx. Overall Diameter
|
Approx. Cable weight
| ||||||||
mm2
|
No./mm
|
mm
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||||||
1.5
|
7/0.53
|
1.59
|
0.7
|
12.3
|
170
|
16.5
|
420
| ||||||||
2.5
|
7/0.67
|
2.01
|
0.7
|
13.8
|
200
|
17.0
|
500
| ||||||||
4
|
7/0.85
|
2.55
|
0.7
|
15.2
|
300
|
18.5
|
600
| ||||||||
6
|
7/1.04
|
3.12
|
0.7
|
16.8
|
380
|
19.8
|
785
| ||||||||
10
|
7/1.35
|
4.05
|
0.7
|
18.0
|
550
|
22.6
|
1030
| ||||||||
16
|
1/1.70
|
5.10
|
0.7
|
21.0
|
760
|
25.0
|
1370
| ||||||||
25
|
7/2.14
|
6.42
|
0.9
|
22.0
|
960
|
29.0
|
1900
| ||||||||
35
|
19/1.53
|
7.65
|
0.9
|
24.0
|
1300
|
32.0
|
2300
| ||||||||
50
|
19/1.78
|
8.90
|
1.0
|
28.0
|
1700
|
35.0
|
2900
| ||||||||
70
|
19/2.14
|
10.70
|
1.1
|
31.0
|
2400
|
40.0
|
4000
| ||||||||
95
|
19/2.52
|
12.60
|
1.1
|
36.0
|
3250
|
45.0
|
5400
| ||||||||
120
|
37/2.03
|
14.21
|
1.2
|
38.0
|
4000
|
49.0
|
6450
| ||||||||
150
|
37/2.25
|
15.75
|
1.4
|
42.0
|
5000
|
55.0
|
8200
| ||||||||
185
|
37/2.52
|
17.64
|
1.6
|
47.0
|
6100
|
60.0
|
9800
| ||||||||
240
|
61/2.25
|
20.25
|
1.7
|
52.0
|
8000
|
68.0
|
12300
| ||||||||
300
|
61/2.52
|
22.68
|
1.8
|
59.0
|
9850
|
74.0
|
14800
| ||||||||
400
|
61/2.85
|
25.65
|
2.0
|
63.0
|
13000
|
83.0
|
17600
|
4-CORE
| |||||||||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| ||||||||||||
Nominal Area
|
No./Dia of Strand
|
Dia. of Conductor
|
Thickness
|
Approx. Overall Diameter
|
Approx. Cable weight
|
Approx. Overall Diameter
|
Approx. Cable weight
| ||||||||
mm2
|
No./mm
|
mm
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||||||
1.5
|
7/0.53
|
1.59
|
0.7
|
14.3
|
210
|
16.0
|
475
| ||||||||
2.5
|
7/0.67
|
2.01
|
0.7
|
15.2
|
270
|
17.8
|
570
| ||||||||
4
|
7/0.85
|
2.55
|
0.7
|
17.2
|
380
|
19.8
|
690
| ||||||||
6
|
7/1.04
|
3.12
|
0.7
|
19.0
|
440
|
21.0
|
940
| ||||||||
10
|
7/1.35
|
4.05
|
0.7
|
20.6
|
670
|
23.3
|
1200
| ||||||||
16
|
1/1.70
|
5.10
|
0.7
|
23.6
|
820
|
26.5
|
1400
| ||||||||
25
|
7/2.14
|
6.42
|
0.9
|
26.0
|
1320
|
30.5
|
2400
| ||||||||
35
|
19/1.53
|
7.65
|
0.9
|
29.0
|
1730
|
34.0
|
2800
| ||||||||
50
|
19/1.78
|
8.90
|
1.0
|
32.0
|
2300
|
38.0
|
3500
| ||||||||
70
|
19/2.14
|
10.70
|
1.1
|
38.0
|
3180
|
44.0
|
5300
| ||||||||
95
|
19/2.52
|
12.60
|
1.1
|
41.9
|
4370
|
48.5
|
6700
| ||||||||
120
|
37/2.03
|
14.21
|
1.2
|
44.0
|
5400
|
54.0
|
8500
| ||||||||
150
|
37/2.25
|
15.75
|
1.4
|
50.8
|
6500
|
59.0
|
10000
| ||||||||
185
|
37/2.52
|
17.64
|
1.6
|
55.0
|
8200
|
64.5
|
12200
| ||||||||
240
|
61/2.25
|
20.25
|
1.7
|
60.5
|
10600
|
74.0
|
15400
| ||||||||
300
|
61/2.52
|
22.68
|
1.8
|
68.5
|
13200
|
82.0
|
19500
| ||||||||
400
|
61/2.85
|
25.65
|
2.0
|
76.0
|
17000
|
92.0
|
25500
|
Multi-Core Cables with XLPE (or LSZH) Insulation, PVC (or LSZH) Outsheath 300/500V or 600/1000V
Current-Carrying Capacities (Amp) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
Current-Carrying Capacities (Amp) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
Conductor Operating Temperature : 90°C | BS 7211 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor cross-sectional area
|
Reference Method 4 (enclosed in an conduit insulated wall etc)
|
Reference Method 3
(enclosed in conduit on a wall or ceiling, or in trunking) |
Reference Method 1 (clipped direct)
|
Reference Method 11
(on a perforated cable tray), or Reference Method 13 (free air) | |||
one 3-core cable or one 4-core cable 3-phase a.c.
|
one 2-core cable singlephase a.c. or d.c.
|
one 3-core cable or one 4-core cable 3-phase a.c.
|
one 2-core cable singlephase a.c. or d.c.
|
one 3-core cable or one 4-core cable 3-phase a.c.
|
one 2-core
cable singlephase a.c. or d.c. |
one 3-core
cable or one 4-core cable 3-phase a.c. | |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1.5
|
16.5
|
22
|
19.5
|
24
|
22
|
26
|
23
|
2.5
|
22
|
30
|
26
|
33
|
30
|
36
|
32
|
4
|
30
|
40
|
35
|
45
|
40
|
49
|
42
|
6
|
38
|
51
|
44
|
58
|
52
|
63
|
54
|
10
|
51
|
69
|
60
|
80
|
71
|
86
|
75
|
16
|
68
|
91
|
80
|
107
|
96
|
115
|
100
|
25
|
89
|
119
|
105
|
138
|
119
|
149
|
127
|
35
|
109
|
146
|
128
|
171
|
147
|
185
|
158
|
50
|
130
|
175
|
154
|
209
|
179
|
225
|
192
|
70
|
164
|
221
|
194
|
269
|
229
|
289
|
246
|
95
|
197
|
265
|
233
|
328
|
278
|
352
|
298
|
120
|
227
|
305
|
268
|
382
|
322
|
410
|
346
|
150
|
259
|
334
|
300
|
441
|
371
|
473
|
399
|
185
|
295
|
384
|
340
|
506
|
424
|
542
|
456
|
240
|
346
|
459
|
398
|
599
|
500
|
641
|
538
|
300
|
396
|
532
|
455
|
693
|
576
|
741
|
621
|
400
|
-
|
625
|
536
|
803
|
667
|
865
|
741
|
Voltage Drop (Per Amp Per Meter) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
Conductor Operating Temperature : 90°C | BS 7211 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor cross-sectional area
|
2-core cable d.c.
|
2-core cable single-phase a.c
|
3-core or 4-core cable 3-phase a.c.
| ||||
1
|
2
|
3
|
4
| ||||
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
| ||||
1.5
|
31
|
31
|
27
| ||||
2.5
|
19
|
19
|
16
| ||||
4
|
12
|
12
|
10
| ||||
6
|
7.9
|
7.9
|
6.8
| ||||
10
|
4.7
|
4.7
|
4.0
| ||||
16
|
2.9
|
2.9
|
2.5
| ||||
r
|
x
|
z
|
r
|
x
|
z
| ||
25
|
1.85
|
1.85
|
0.16
|
1.90
|
1.6
|
0.14
|
1.65
|
35
|
1.35
|
1.35
|
0.155
|
1.35
|
1.15
|
0.135
|
1.15
|
50
|
0.98
|
0.99
|
0.155
|
1.00
|
0.86
|
0.135
|
0.87
|
70
|
0.67
|
0.67
|
0.150
|
0.69
|
0.59
|
0.130
|
0.60
|
95
|
0.49
|
0.50
|
0.150
|
0.52
|
0.43
|
0.130
|
0.45
|
120
|
0.39
|
0.40
|
0.145
|
0.42
|
0.34
|
0.130
|
0.37
|
150
|
0.31
|
0.32
|
0.145
|
0.35
|
0.28
|
0.125
|
0.30
|
185
|
0.25
|
0.26
|
0.145
|
0.29
|
0.22
|
0.125
|
0.26
|
240
|
0.195
|
0.20
|
0.140
|
0.24
|
0.175
|
0.125
|
0.21
|
300
|
0.155
|
0.16
|
0.140
|
0.21
|
0.140
|
0.120
|
0.185
|
400
|
0.120
|
0.13
|
0.140
|
0.19
|
0.115
|
0.120
|
0.165
|
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
r = conductor resistance at operating temperature
x = reactance
z = impedance
Multi-Core Cables with XLPE (or LSZH) Insulation, Armoured, PVC or LSZH Outsheath 600/1000V
Current-Carrying Capacities (Amp) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables]
Current-Carrying Capacities (Amp) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables]
BS 6724 | |
Conductor Operating Temperature : 90°C | BS 7846 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor
cross-sectional area |
Reference Method 1 (clipped
direct) |
Reference Method 11 (on a
perforated horizontal cable tray or Reference Method 13 [free air] ) |
In single-way ducts
|
Laid direct in ground
| ||||
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
|
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
|
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
|
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
| |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1.5
|
27
|
23
|
29
|
25
|
-
|
23
|
-
|
28
|
2.5
|
36
|
31
|
39
|
33
|
-
|
30
|
-
|
36
|
4
|
49
|
42
|
52
|
44
|
-
|
40
|
-
|
48
|
6
|
62
|
53
|
66
|
56
|
-
|
50
|
-
|
60
|
10
|
85
|
73
|
90
|
78
|
-
|
65
|
-
|
80
|
16
|
110
|
94
|
115
|
99
|
115
|
94
|
140
|
115
|
25
|
146
|
124
|
152
|
131
|
145
|
125
|
180
|
150
|
35
|
180
|
154
|
188
|
162
|
175
|
150
|
215
|
180
|
50
|
219
|
187
|
228
|
197
|
210
|
175
|
255
|
215
|
70
|
279
|
238
|
291
|
251
|
260
|
215
|
315
|
265
|
95
|
338
|
289
|
354
|
304
|
310
|
260
|
380
|
315
|
120
|
392
|
335
|
410
|
353
|
355
|
300
|
430
|
360
|
150
|
451
|
386
|
472
|
406
|
400
|
335
|
480
|
405
|
185
|
515
|
441
|
539
|
463
|
455
|
380
|
540
|
460
|
240
|
607
|
520
|
636
|
546
|
520
|
440
|
630
|
530
|
300
|
698
|
599
|
732
|
628
|
590
|
495
|
700
|
590
|
400
|
787
|
673
|
847
|
728
|
660
|
560
|
790
|
670
|
Voltage Drop (Per Amp Per Meter) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables
BS 6724 | |
Conductor Operating Temperature : 90°C | BS 7846 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor
cross-sectional area |
2-core cable d.c.
|
2 cables, single-phase a.c.
|
3 or 4 cables, 3-phase a.c.
|
2 cables,
single-phase a.c. |
3 or 4 cables,
3-phase a.c. | ||||
In ducts or
in ground |
In ducts or
in ground | ||||||||
1
|
2
|
3
|
4
|
5
|
6
| ||||
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
| ||||
1.5
|
31.0
|
31.0
|
27.0
|
31.0
|
25.0
| ||||
2.5
|
19.0
|
19.0
|
16.0
|
19.0
|
15.0
| ||||
4
|
12.0
|
12.0
|
10.0
|
12.0
|
9.7
| ||||
6
|
7.9
|
7.9
|
6.8
|
7.9
|
6.5
| ||||
10
|
4.7
|
4.7
|
4.0
|
4.7
|
3.9
| ||||
16
|
2.9
|
2.9
|
2.5
|
2.9
|
2.6
| ||||
r
|
x
|
z
|
r
|
x
|
z
| ||||
25
|
1.850
|
1.350
|
0.160
|
1.900
|
1.600
|
0.140
|
1.650
|
1.900
|
1.600
|
35
|
1.350
|
1.350
|
0.155
|
1.350
|
1.150
|
0.135
|
1.150
|
1.350
|
1.200
|
50
|
0.980
|
0.990
|
0.155
|
1.000
|
0.860
|
0.135
|
0.870
|
1.000
|
0.870
|
70
|
0.670
|
0.670
|
0.150
|
0.690
|
0.590
|
0.130
|
0.600
|
0.690
|
0.610
|
95
|
0.490
|
0.500
|
0.150
|
0.520
|
0.430
|
0.130
|
0.450
|
0.520
|
0.450
|
120
|
0.390
|
0.400
|
0.145
|
0.420
|
0.340
|
0.130
|
0.370
|
0.420
|
0.360
|
150
|
0.310
|
0.320
|
0.145
|
0.350
|
0.280
|
0.125
|
0.300
|
0.350
|
0.300
|
185
|
0.250
|
0.260
|
0.145
|
0.290
|
0.220
|
0.125
|
0.260
|
0.290
|
0.250
|
240
|
0.195
|
0.200
|
0.140
|
0.240
|
0.175
|
0.125
|
0.210
|
0.240
|
0.210
|
300
|
0.155
|
0.160
|
0.140
|
0.210
|
0.140
|
0.120
|
0.185
|
0.210
|
0.190
|
400
|
0.120
|
0.130
|
0.140
|
0.190
|
0.115
|
0.120
|
0.165
|
0.190
|
0.180
|
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
r = conductor resistance at operating temperature
x = reactance
z = impedance
No comments: