Low Voltage Cables
600 / 1000V 2-Core ~ 4-Core
PVC Insulated, Unarmoured & Armoured
PVC Sheathed Cable
APPLICATION |
This cable is primarily used for main power supply. It can be installed in cable ducts, on cable trays, on cable ladders and in cable trunking. The armoured cable is ideal for ground emplacement if a higher electrical or mechanical protection is required.
|
VOLTAGE RATING |
600/1000V
|
CONSTRUCTION |
Plain annealed copper, PVC insulated, unarmoured or galvanized steel wires armoured, PVC sheathed cable
|
INSULATION COLOUR |
|
SHEATH COLOUR |
Black
|
SPECIFICATION |
BS6346, IEC60502-1
|
- Detailed Specification
- Current Rating and Voltage Drop
2-CORE
| |||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| ||||||
Nominal Area
|
Thickness
|
Approx. Overall Diameter
|
Approx. Cable Weight
|
Approx. Overall Diameter
|
Approx. Cable Weight
| ||||
mm2
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||
1.5 (cs)
|
0.8
|
11.2
|
150
|
12.1
|
290
| ||||
2.5 (cs)
|
0.8
|
11.6
|
180
|
13.3
|
340
| ||||
4 (cs)
|
1.0
|
13.7
|
260
|
15.4
|
470
| ||||
6 (cs)
|
1.0
|
15.2
|
290
|
16.8
|
550
| ||||
10 (cs)
|
1.0
|
16.1
|
450
|
20.8
|
860
| ||||
16 (cs)
|
1.0
|
18.2
|
550
|
22.1
|
1080
| ||||
25 (s)
|
1.2
|
19.0
|
680
|
23.0
|
1440
| ||||
35 (s)
|
1.2
|
21.0
|
940
|
25.0
|
1600
| ||||
50 (s)
|
1.4
|
23.0
|
1250
|
28.0
|
1990
| ||||
70 (s)
|
1.4
|
26.0
|
1700
|
30.6
|
2550
| ||||
95 (s)
|
1.6
|
29.3
|
2330
|
35.8
|
3630
| ||||
120 (s)
|
1.6
|
31.8
|
2860
|
38.3
|
4220
| ||||
150 (s)
|
1.8
|
35.1
|
3550
|
41.5
|
5020
| ||||
185 (s)
|
2.0
|
39.1
|
4360
|
46.4
|
6530
| ||||
240 (s)
|
2.2
|
43.9
|
5550
|
51.2
|
8190
| ||||
300 (s)
|
2.4
|
48.7
|
6910
|
56.4
|
9860
| ||||
400 (s)
|
2.6
|
54.2
|
8600
|
61.9
|
11190
|
(cs) : Circular Stranded
(s) : Sector Shaped Stranded Conductors
(s) : Sector Shaped Stranded Conductors
3-CORE
| |||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| ||||||
Nominal Area
|
Thickness
|
Approx. Overall Diameter
|
Approx. Cable Weight
|
Approx. Overall Diameter
|
Approx. Cable Weight
| ||||
mm2
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||
1.5 (cs)
|
0.8
|
11.3
|
165
|
12.9
|
305
| ||||
2.5 (cs)
|
0.8
|
12.3
|
200
|
14.4
|
390
| ||||
4 (cs)
|
1.0
|
14.2
|
300
|
16.0
|
520
| ||||
6 (cs)
|
1.0
|
15.8
|
380
|
18.1
|
705
| ||||
10 (cs)
|
1.0
|
17.0
|
545
|
21.1
|
945
| ||||
16 (cs)
|
1.0
|
19.7
|
760
|
23.5
|
1220
| ||||
25 (s)
|
1.2
|
21.0
|
955
|
26.0
|
1700
| ||||
35 (s)
|
1.2
|
23.0
|
1300
|
27.0
|
2100
| ||||
50 (s)
|
1.4
|
26.5
|
1720
|
31.0
|
2560
| ||||
70 (s)
|
1.4
|
29.5
|
2380
|
35.0
|
3360
| ||||
95 (s)
|
1.6
|
35.0
|
3245
|
39.1
|
4630
| ||||
120 (s)
|
1.6
|
37.0
|
4030
|
42.1
|
5710
| ||||
150 (s)
|
1.8
|
41.0
|
5000
|
47.3
|
7160
| ||||
185 (s)
|
2.0
|
46.0
|
6140
|
51.9
|
8510
| ||||
240 (s)
|
2.2
|
51.0
|
7960
|
57.8
|
10790
| ||||
300 (s)
|
2.4
|
58.0
|
9850
|
63.2
|
12940
| ||||
400 (s)
|
2.6
|
62.0
|
12990
|
69.6
|
16970
|
(cs) : Circular Stranded
(s) : Sector Shaped Stranded Conductors
(s) : Sector Shaped Stranded Conductors
4-CORE
| |||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| ||||||
Nominal Area
|
Thickness
|
Approx. Overall Diameter
|
Approx. Cable Weight
|
Approx. Overall Diameter
|
Approx. Cable Weight
| ||||
mm2
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||
1.5 (cs)
|
0.8
|
12.3
|
210
|
13.5
|
345
| ||||
2.5 (cs)
|
0.8
|
13.2
|
265
|
15.0
|
375
| ||||
4 (cs)
|
1.0
|
15.2
|
385
|
17.5
|
690
| ||||
6 (cs)
|
1.0
|
16.9
|
440
|
19.5
|
835
| ||||
10 (cs)
|
1.0
|
18.6
|
675
|
22.9
|
1130
| ||||
16 (cs)
|
1.0
|
21.6
|
925
|
26.5
|
1700
| ||||
25 (s)
|
1.2
|
24.0
|
1320
|
28.0
|
2100
| ||||
35 (s)
|
1.2
|
26.5
|
1740
|
31.0
|
2540
| ||||
50 (s)
|
1.4
|
30.0
|
2300
|
35.4
|
3500
| ||||
70 (s)
|
1.4
|
34.0
|
3180
|
39.2
|
4610
| ||||
95 (s)
|
1.6
|
38.3
|
4370
|
44.4
|
5950
| ||||
120 (s)
|
1.6
|
41.8
|
5400
|
49.1
|
7610
| ||||
150 (s)
|
1.8
|
47.5
|
6550
|
53.8
|
9000
| ||||
185 (s)
|
2.0
|
52.0
|
8180
|
59.2
|
10900
| ||||
240 (s)
|
2.2
|
58.0
|
10700
|
66.7
|
13600
| ||||
300 (s)
|
2.4
|
66.0
|
13200
|
72.0
|
16500
| ||||
400 (s)
|
2.6
|
73.5
|
17100
|
81.3
|
23000
|
(cs) : Circular Stranded
(s) : Sector Shaped Stranded Conductors
(s) : Sector Shaped Stranded Conductors
Multi-Core Cables with PVC Insulation, Unarmoured, PVC Outsheath 600/1000V
Current-Carrying Capacities (Amp) [CU/PVC/PVC Cables]
Current-Carrying Capacities (Amp) [CU/PVC/PVC Cables]
BS 6004 | |
Conductor Operating Temperature : 70°C | BS 6346 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor
cross-sectional area |
Reference Method 4
(enclosed in an insulated wall etc) |
Reference Method 3
(enclosed in conduit on a wall or ceiling, or in trunking) |
Reference Method 1
(clipped direct) |
Reference Method 11 (on
perforated cable tray), or Reference Method 13 (free air) | ||||
one 2-core
cable* singlephase a.c. or d.c. |
one 3-core
cable* or one 4-core cable 3-phase a.c. |
one 2-core
cable* singlephase a.c. or d.c. |
one 3-core
cable* or one 4-core cable 3-phase a.c. |
one 2-core
cable* singlephase a.c. or d.c. |
one 3-core
cable* or one 4-core cable 3-phase a.c. |
one 2-core
cable* singlephase a.c. or d.c. |
one 3-core
cable* or one 4-core cable 3-phase a.c. | |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1
|
11
|
10
|
13
|
11.5
|
15
|
13.5
|
17
|
14.5
|
1.5
|
14
|
13
|
16.5
|
15
|
19.5
|
17.
|
5 22
|
18.5
|
2.5
|
18.5
|
17.5
|
23
|
20
|
27
|
24
|
30
|
25
|
4
|
25
|
23
|
30
|
27
|
36
|
32
|
40
|
34
|
6
|
32
|
29
|
38
|
34
|
46
|
41
|
51
|
43
|
10
|
43
|
39
|
52
|
46
|
63
|
57
|
70
|
60
|
16
|
57
|
52
|
69
|
62
|
85
|
76
|
94
|
80
|
25
|
75
|
68
|
90
|
80
|
112
|
96
|
119
|
101
|
35
|
92
|
83
|
111
|
99
|
138
|
119
|
148
|
126
|
50
|
110
|
99
|
133
|
118
|
168
|
144
|
180
|
153
|
70
|
139
|
125
|
168
|
149
|
213
|
184
|
232
|
196
|
95
|
167
|
150
|
201
|
179
|
258
|
223
|
282
|
238
|
120
|
192
|
172
|
232
|
206
|
299
|
259
|
328
|
276
|
150
|
219
|
196
|
258
|
225
|
344
|
299
|
379
|
319
|
185
|
248
|
223
|
294
|
255
|
392
|
341
|
434
|
364
|
240
|
291
|
261
|
344
|
297
|
461
|
403
|
514
|
430
|
300
|
334
|
298
|
394
|
339
|
530
|
464
|
593
|
497
|
400
|
-
|
-
|
470
|
402
|
634
|
557
|
715
|
597
|
* With or without protective conductor
Voltage Drop (Per Amp Per Meter) [PVC/PVC Cables]
Conductor Operating Temperature : 70°C | |
Ambient Temperature : 30°C |
Conductor
cross-sectional area |
2-core cable a.c.
|
2-core cable single-phase a.c.
|
3-core or 4-core cable 3-phase a.c.
| ||||
1
|
2
|
3
|
4
| ||||
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
| ||||
1
|
44
|
44
|
38
| ||||
1.5
|
29
|
29
|
25
| ||||
2.5
|
18
|
18
|
15
| ||||
4
|
11
|
11
|
9.5
| ||||
6
|
7.3
|
7.3
|
6.4
| ||||
10
|
4.4
|
4.4
|
3.8
| ||||
16
|
2.8
|
2.8
|
2.4
| ||||
r
|
x
|
z
|
r
|
x
|
z
| ||
25
|
1.75
|
1.75
|
0.170
|
1.75
|
1.50
|
0.145
|
1.50
|
35
|
1.25
|
1.25
|
0.165
|
1.25
|
1.10
|
0.145
|
1.10
|
50
|
0.93
|
0.93
|
0.165
|
0.94
|
0.80
|
0.140
|
0.81
|
70
|
0.63
|
0.63
|
0.160
|
0.65
|
0.55
|
0.140
|
0.57
|
95
|
0.46
|
0.47
|
0.155
|
0.50
|
0.41
|
0.135
|
0.43
|
120
|
0.36
|
0.38
|
0.155
|
0.41
|
0.33
|
0.135
|
0.35
|
150
|
0.29
|
0.30
|
0.155
|
0.34
|
0.26
|
0.130
|
0.29
|
185
|
0.23
|
0.25
|
0.150
|
0.29
|
0.21
|
0.130
|
0.25
|
240
|
0.180
|
0.190
|
0.150
|
0.24
|
0.165
|
0.130
|
0.21
|
300
|
0.145
|
0.155
|
0.145
|
0.21
|
0.135
|
0.130
|
0.185
|
400
|
0.105
|
0.115
|
0.145
|
0.185
|
0.100
|
0.125
|
0.160
|
Multi-Core Cables with PVC Insulation, Armoured, PVC Outsheath 600/1000V
Current-Carrying Capacities (Amp) [CU/PVC/SWA/PVC Cable]
Current-Carrying Capacities (Amp) [CU/PVC/SWA/PVC Cable]
Conductor Operating Temperature : 70°C | BS 6346 |
Ambient Temperature : 30°C |
Conductor cross-sectional
area |
Reference Method 1 (clipped
direct) |
Reference Method 11 (on a
perforated horizontal cable tray or Reference Method 13 [free air] ) |
Direct in ground
|
In single way ducts
| ||||
one 2-core
cable singlephase a.c. or d.c. |
one 3-core or
4-core cable 3-phase a.c. |
one 2-core
cable singlephase a.c. or d.c. |
one 3-core or
4-core cable 3-phase a.c. |
2-core
|
3-core or
4-core |
2-core
|
3-core or
4-core | |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1.5
|
21
|
18
|
22
|
19
|
32
|
27
|
26
|
22
|
2.5
|
28
|
25
|
31
|
26
|
41
|
35
|
34
|
29
|
4
|
38
|
33
|
41
|
35
|
55
|
47
|
45
|
38
|
6
|
49
|
42
|
53
|
45
|
69
|
59
|
57
|
48
|
10
|
67
|
58
|
72
|
62
|
92
|
78
|
76
|
64
|
16
|
89
|
77
|
97
|
83
|
119
|
101
|
98
|
83
|
25
|
118
|
102
|
128
|
110
|
158
|
132
|
129
|
107
|
35
|
145
|
125
|
157
|
135
|
190
|
159
|
154
|
126
|
50
|
175
|
151
|
190
|
163
|
225
|
188
|
183
|
153
|
70
|
222
|
192
|
241
|
207
|
277
|
233
|
225
|
190
|
95
|
269
|
231
|
291
|
251
|
332
|
279
|
271
|
228
|
120
|
310
|
267
|
336
|
290
|
377
|
317
|
309
|
260
|
150
|
356
|
306
|
386
|
332
|
422
|
355
|
346
|
292
|
185
|
405
|
348
|
439
|
378
|
478
|
401
|
393
|
331
|
240
|
476
|
409
|
516
|
445
|
551
|
462
|
455
|
382
|
300
|
547
|
469
|
592
|
510
|
616
|
517
|
510
|
428
|
400
|
621
|
540
|
683
|
590
|
693
|
580
|
574
|
490
|
Voltage Drop (Per Amp Per Meter) [PVC/PVC Cables]
Conductor Operating Temperature : 70°C | BS 6346 |
Ambient Temperature : 30°C |
Conductor
cross-sectional area |
2-core
cable a.c. |
2-core cable single-phase a.c.
|
2-core cable single-phase a.c. 3
|
Direct in ground
|
Direct in ground
| ||||||
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
| ||||
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
| ||||
1.5
|
29
|
29
|
25
|
29
|
25
|
29
|
25
| ||||
2.5
|
18
|
18
|
15
|
18
|
15
|
18
|
15
| ||||
4
|
11
|
11
|
9.5
|
11
|
9.5
|
11
|
9.5
| ||||
6
|
7.3
|
7.3
|
6.4
|
7.4
|
6.4
|
7.4
|
6.4
| ||||
10
|
4.4
|
4.4
|
3.8
|
4.4
|
3.8
|
4.4
|
3.8
| ||||
16
|
2.8
|
2.8
|
2.4
|
2.8
|
2.4
|
2.8
|
2.4
| ||||
r
|
x
|
z
|
r
|
x
|
z
| ||||||
25
|
1.75
|
1.75
|
0.17
|
1.75
|
1.5
|
0.145
|
1.5
|
1.7
|
1.5
|
1.7
|
1.5
|
35
|
1.25
|
1.25
|
0.165
|
1.25
|
1.1
|
0.145
|
1.1
|
1.3
|
1.1
|
1.3
|
1.1
|
50
|
0.93
|
0.93
|
0.165
|
0.94
|
0.8
|
0.14
|
0.81
|
0.94
|
0.82
|
0.94
|
0.82
|
70
|
0.63
|
0.63
|
0.16
|
0.65
|
0.55
|
0.14
|
0.57
|
0.66
|
0.57
|
0.66
|
0.57
|
95
|
0.46
|
0.47
|
0.155
|
0.5
|
0.41
|
0.135
|
0.43
|
0.49
|
0.42
|
0.49
|
0.42
|
120
|
0.36
|
0.38
|
0.155
|
0.41
|
0.33
|
0.135
|
0.35
|
0.4
|
0.35
|
0.40
|
0.35
|
150
|
0.29
|
0.30
|
0.155
|
0.34
|
0.26
|
0.13
|
0.29
|
0.34
|
0.29
|
0.34
|
0.29
|
185
|
0.23
|
0.25
|
0.15
|
0.29
|
0.21
|
0.13
|
0.25
|
0.29
|
0.25
|
0.29
|
0.25
|
240
|
0.18
|
0.19
|
0.15
|
0.24
|
0.165
|
0.13
|
0.21
|
0.24
|
0.21
|
0.24
|
0.21
|
300
|
0.145
|
0.155
|
0.145
|
0.21
|
0.135
|
0.13
|
0.185
|
0.21
|
0.18
|
0.21
|
0.18
|
400
|
0.105
|
0.115
|
0.145
|
0.185
|
0.1
|
0.125
|
0.16
|
0.19
|
0.17
|
0.19
|
0.17
|
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
r = conductor resistance at operating temperature
x = reactance
z = impedance
No comments: