Low Voltage Cables
600 / 1000V Single-Core, Mica Tape Fire Barrier
XLPE Insulated, Unarmoured & Armoured
LSZH Sheathed, Fire Resistant Cable
APPLICATION |
This cable is designed for areas where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground tunnels, communications systems, sewage treatment plants, lifts, escalators, and high-rise buildings.
|
VOLTAGE RATING |
600/1000V
|
CONSTRUCTION |
Plain annealed copper, mica tape fire barrier, XLPE or XLEVA compound insulated, unarmoured or aluminum wires armoured, LSZH compound sheathed cable
|
INSULATION COLOUR |
Natural
|
SHEATH COLOUR |
Orange or as per order
|
SPECIFICATION |
BS6724, BS6387, SS299-1, IEC60502-1, IEC60331, IEC60332-1, IEC60332-3, IEC60754, IEC61034
|
- Detailed Specification
- Current Rating and Voltage Drop
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| ||||||||
Nominal Area
|
No./Dia of Strand
|
Dia. of Conductor
|
Thickness
|
Approx. Overall Diameter
|
Approx. Cable weight
|
Approx. Overall Diameter
|
Approx Cable weight
| ||||
mm2
|
No./mm
|
mm
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||
1.5
|
7/0.53
|
1.59
|
0.7
|
6.5
|
54
|
-
|
-
| ||||
2.5
|
7/0.67
|
2.01
|
0.7
|
6.8
|
67
|
-
|
-
| ||||
4
|
7/0.85
|
2.55
|
0.7
|
7.5
|
86
|
-
|
-
| ||||
6
|
7/1.04
|
3.12
|
0.7
|
8.1
|
110
|
-
|
-
| ||||
10
|
7/1.35
|
4.05
|
0.7
|
9.2
|
155
|
-
|
-
| ||||
16
|
7/1.70
|
5.10
|
0.7
|
10.2
|
220
|
-
|
-
| ||||
25
|
7/2.14
|
6.42
|
0.9
|
11.9
|
325
|
-
|
-
| ||||
35
|
19/1.53
|
7.65
|
0.9
|
13.2
|
425
|
-
|
-
| ||||
50
|
19/1.78
|
8.90
|
1.0
|
14.6
|
600
|
18.5
|
780
| ||||
70
|
19/2.14
|
10.70
|
1.1
|
16.6
|
820
|
20.5
|
1010
| ||||
95
|
19/2.52
|
12.60
|
1.1
|
18.7
|
1100
|
23.0
|
1320
| ||||
120
|
37/2.03
|
14.21
|
1.2
|
20.5
|
1350
|
24.5
|
1610
| ||||
150
|
37/2.25
|
15.75
|
1.4
|
22.7
|
1640
|
27.0
|
2010
| ||||
185
|
37.2.52
|
17.64
|
1.6
|
25.5
|
2040
|
29.5
|
2440
| ||||
240
|
61/2.25
|
20.25
|
1.7
|
28.5
|
2650
|
34.5
|
3060
| ||||
300
|
61/2.52
|
22.68
|
1.8
|
31.5
|
3260
|
36.9
|
3690
| ||||
400
|
65/2.85
|
25.65
|
2.0
|
35.4
|
4130
|
41.5
|
4780
| ||||
500
|
61/3.20
|
28.80
|
2.2
|
39.0
|
5200
|
45.5
|
5970
| ||||
630
|
127/2.52
|
32.76
|
2.4
|
43.5
|
6600
|
50.5
|
7530
| ||||
800
|
127/2.85
|
37.05
|
2.6
|
48.5
|
8300
|
56.8
|
9680
| ||||
1000
|
127/3.20
|
41.60
|
2.8
|
53.5
|
10000
|
61.5
|
11980
|
Single-Core Cables with XLPE (or LSZH) Insulation, with or without PVC (or LSZH) Outsheath 450/750V or 600/1000V
Current-Carrying Capacities (Amp)
Current-Carrying Capacities (Amp)
Conductor Operating Temperature : 90°C | BS 7211 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor cross-sectional
area |
Reference Method 4 (enclosed in conduit in thermally insulating wall etc)
|
Reference Method 3 (enclosed in conduit on a wall or in trunking etc)
|
Reference Method 1 (clipped direct)
|
Reference Method 11 (on a perforated cable tray, horizontal or vertical)
|
Reference Method 12 (free air)
| ||||||
Horizontal flat spaced
|
Vertical flat spaced
|
Trefoil
| |||||||||
2 cables, single-phase a.c. or d.c.
|
3 or 4 cables, 3-phase a.c.
|
2 cables, single-phase a.c. or d.c
|
3 or 4 cables, 3-phase a.c.
|
2 cables, single-phase a.c. or d.c. flat and touching
|
3 or 4 cables, 3-phase a.c. flat and touching or trefoil
|
2 cables, single-phase a.c. or d.c. or flat and touching
|
3 or 4 cables, 3-phase a.c. flat and touching or trefoil
|
2 cables, single-phase a.c. or d.c. or 3 cables three phase
|
2 cables, single-phase a.c. or d.c. or 3 cables three phase
|
3 cables, trefoil 3-phase a.c.
| |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1.5
|
18
|
17
|
22
|
19
|
25
|
23
|
-
|
-
|
-
|
-
|
-
|
2.5
|
24
|
23
|
30
|
26
|
34
|
31
|
-
|
-
|
-
|
-
|
-
|
4
|
33
|
30
|
40
|
35
|
46
|
41
|
-
|
-
|
-
|
-
|
-
|
6
|
43
|
39
|
51
|
45
|
59
|
54
|
-
|
-
|
-
|
-
|
-
|
10
|
58
|
53
|
71
|
63
|
81
|
74
|
-
|
-
|
-
|
-
|
-
|
16
|
76
|
70
|
95
|
85
|
109
|
99
|
-
|
-
|
-
|
-
|
-
|
25
|
100
|
91
|
126
|
111
|
143
|
130
|
158
|
140
|
183
|
163
|
138
|
35
|
125
|
111
|
156
|
138
|
176
|
161
|
195
|
176
|
226
|
203
|
171
|
50
|
149
|
135
|
189
|
168
|
228
|
209
|
293
|
215
|
274
|
246
|
209
|
70
|
189
|
170
|
240
|
214
|
293
|
268
|
308
|
279
|
351
|
318
|
270
|
95
|
228
|
205
|
290
|
259
|
355
|
326
|
375
|
341
|
426
|
389
|
330
|
120
|
263
|
235
|
336
|
299
|
413
|
379
|
436
|
398
|
495
|
453
|
385
|
150
|
300
|
270
|
375
|
328
|
476
|
436
|
505
|
461
|
570
|
524
|
445
|
185
|
341
|
306
|
426
|
370
|
545
|
500
|
579
|
530
|
651
|
600
|
511
|
240
|
400
|
358
|
500
|
433
|
644
|
590
|
686
|
630
|
769
|
711
|
606
|
300
|
459
|
410
|
573
|
493
|
743
|
681
|
794
|
730
|
886
|
824
|
701
|
400
|
-
|
-
|
684
|
584
|
868
|
793
|
915
|
849
|
1065
|
994
|
820
|
500
|
-
|
-
|
783
|
666
|
990
|
904
|
1044
|
973
|
1228
|
1150
|
936
|
630
|
-
|
-
|
900
|
764
|
1130
|
1033
|
1191
|
1115
|
1423
|
1338
|
1069
|
800
|
-
|
-
|
-
|
-
|
1288
|
1179
|
1358
|
1275
|
1580
|
1485
|
1214
|
1000
|
-
|
-
|
-
|
-
|
1443
|
1323
|
1520
|
1436
|
1775
|
1671
|
1349
|
Voltage Drop (Per Amp Per Meter) [CU/LSZH; CU/XLPE/PVC; CU/XLPE/LSZH or CU/LSZH/LSZH cables]
Conductor Operating Temperature : 90°C | BS 7211 |
Ambient Temperature : 30°C | IEC60502-1 |
Size of conductor
|
2 cables d.c.
|
2 cables, single-phase a.c.
|
3 or 4 cables, 3-phase a.c.
| |||||||||||||
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)
|
Ref. Methods 1 and 11 (clipped direct or on trays touching)
|
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)
|
Ref. Methods 1,
11 and 12 (in trefoil) |
Ref. Methods 1 and 11
(Flat and touching) | ||||||||||||
1
|
2
|
3
|
4
|
5
|
6
|
7
| ||||||||||
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
| ||||||||||
1.5
|
31
|
31
|
27
|
27
|
27
|
27
| ||||||||||
2.5
|
19
|
19
|
16
|
16
|
16
|
16
| ||||||||||
4
|
33
|
12
|
10
|
10
|
10
|
10
| ||||||||||
6
|
7.8
|
7.9
|
6.8
|
6.8
|
6.8
|
6.8
| ||||||||||
10
|
4.7
|
4.7
|
4.7
|
4
|
4
|
4
| ||||||||||
16
|
2.9
|
2.9
|
2.9
|
2.5
|
2.5
|
2.5
| ||||||||||
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
| ||
25
|
1.85
|
1.85
|
0.31
|
1.90
|
1.85
|
0.190
|
1.85
|
1.60
|
0.27
|
1.65
|
1.600
|
0.165
|
1.600
|
1.600
|
0.190
|
1.600
|
35
|
1.35
|
1.35
|
0.29
|
1.35
|
1.35
|
0.180
|
1.35
|
1.15
|
0.25
|
1.15
|
1.150
|
0.155
|
1.50
|
1.150
|
0.180
|
1.150
|
50
|
0.99
|
1.00
|
0.29
|
1.05
|
0.99
|
0.180
|
1.00
|
0.87
|
0.25
|
0.90
|
0.860
|
0.155
|
0.870
|
0.860
|
0.180
|
0.870
|
70
|
0.68
|
0.70
|
0.28
|
0.75
|
0.68
|
0.175
|
0.71
|
0.60
|
0.24
|
0.65
|
0.590
|
0.150
|
0.610
|
0.590
|
0.175
|
0.620
|
95
|
0.49
|
0.51
|
0.27
|
0.58
|
0.49
|
0.170
|
0.52
|
0.44
|
0.23
|
0.50
|
0.430
|
0.145
|
0.450
|
0.430
|
0.170
|
0.460
|
120
|
0.39
|
0.41
|
0.26
|
0.48
|
0.39
|
0.165
|
0.43
|
0.35
|
0.23
|
0.42
|
0.340
|
0.140
|
0.370
|
0.340
|
0.165
|
0.380
|
150
|
0.32
|
0.33
|
0.26
|
0.43
|
0.32
|
0.165
|
0.36
|
0.29
|
0.23
|
0.37
|
0.280
|
0.140
|
0.310
|
0.280
|
0.165
|
0.320
|
185
|
0.25
|
0.27
|
0.26
|
0.37
|
0.26
|
0.165
|
0.30
|
0.23
|
0.23
|
0.32
|
0.220
|
0.140
|
0.260
|
0.220
|
0.165
|
0.280
|
240
|
0.19
|
0.21
|
0.26
|
0.33
|
0.20
|
0.160
|
0.25
|
0.185
|
0.22
|
0.29
|
0.170
|
0.140
|
0.220
|
0.170
|
0.165
|
0.240
|
300
|
0.155
|
0.175
|
0.25
|
0.31
|
0.16
|
0.160
|
0.22
|
0.150
|
0.22
|
0.27
|
0.140
|
0.140
|
0.195
|
0.135
|
0.160
|
0.210
|
400
|
0.12
|
0.140
|
0.25
|
0.29
|
0.13
|
0.155
|
0.20
|
0.125
|
0.22
|
0.25
|
0.110
|
0.135
|
0.175
|
0.110
|
0.160
|
0.195
|
500
|
0.093
|
0.120
|
0.25
|
0.28
|
0.105
|
0.155
|
0.185
|
0.100
|
0.22
|
0.24
|
0.090
|
0.135
|
0.160
|
0.088
|
0.160
|
0.180
|
630
|
0.072
|
0.100
|
0.25
|
0.27
|
0.086
|
0.155
|
0.175
|
0.088
|
0.21
|
0.23
|
0.074
|
0.135
|
0.150
|
0.071
|
0.160
|
0.170
|
800
|
0.056
|
-
|
-
|
-
|
0.072
|
0.150
|
0.170
|
-
|
-
|
-
|
0.062
|
0.130
|
0.145
|
0.059
|
0.155
|
0.165
|
1000
|
0.045
|
-
|
-
|
-
|
0.063
|
0.150
|
0.165
|
-
|
-
|
-
|
0.055
|
0.130
|
0.140
|
0.050
|
0.155
|
0.165
|
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
r = conductor resistance at operating temperature
x = reactance
z = impedance
Single Core Cables with XLPE or LSZH Insulation, Armoured, PVC or LSZH Outsheath 600/1000V
Current-Carrying Capacities (Amp) [CU/XLPE/AWA/PVC or CU/XLPE/AWA/LSZH Cables]
Current-Carrying Capacities (Amp) [CU/XLPE/AWA/PVC or CU/XLPE/AWA/LSZH Cables]
BS 6724 | |
Conductor Operating Temperature : 90°C | BS 7846 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor
cross-sectional area |
Reference Method 1
(clipped direct) |
Reference Method 11 (on
perforated cable tray) |
Reference
Method 12 (free air) |
In single-way ducts
|
Laid direct in ground
| ||||
2 cables
singlephase a.c. or d.c. flat and touching |
3 or 4
cables 3-phase a.c. flat and touching |
2 cables
singlephase a.c. or d.c. flat and touching |
3 or 4
cables 3-phase a.c. flat and touching |
3 cables
3-phase a.c. trefoil touching |
2 cables
singlephase a.c. or d.c. ducts touching |
3 cables
3-phase a.c. trefoil touching |
2 cables
singlephase a.c. or d.c. touching |
3 cables
3-phase a.c. trefoil touching | |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
50
|
237
|
220
|
253
|
232
|
222
|
255
|
235
|
275
|
235
|
70
|
303
|
277
|
322
|
293
|
285
|
310
|
280
|
340
|
290
|
95
|
367
|
333
|
389
|
352
|
346
|
365
|
330
|
405
|
345
|
120
|
425
|
383
|
449
|
405
|
402
|
410
|
370
|
460
|
389
|
150
|
488
|
437
|
516
|
462
|
463
|
445
|
405
|
510
|
435
|
185
|
557
|
496
|
587
|
524
|
529
|
485
|
440
|
580
|
490
|
240
|
656
|
579
|
689
|
612
|
625
|
550
|
500
|
670
|
560
|
300
|
755
|
662
|
792
|
700
|
720
|
610
|
550
|
750
|
630
|
400
|
853
|
717
|
899
|
767
|
815
|
640
|
580
|
830
|
700
|
500
|
962
|
791
|
1016
|
851
|
918
|
690
|
620
|
910
|
770
|
630
|
1082
|
861
|
1146
|
935
|
1027
|
750
|
670
|
1000
|
840
|
800
|
1170
|
904
|
1246
|
987
|
1119
|
828
|
735
|
1117
|
931
|
1000
|
1261
|
961
|
1345
|
1055
|
1214
|
919
|
811
|
1254
|
1038
|
Voltage Drop (Per Amp Per Meter) [CU/XLPE/AWA/PVC or CU/XLPE/AWA/LSZH Cables]
BS 6724 | |
Conductor Operating Temperature : 90°C | BS 7846 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor
cross-sectional area |
2 cables
d.c. |
2 cables single-phase
a.c. |
3 or 4 cables three-phase a.c.
|
2 cables singlephase
a.c. |
3 or 4 cables,
3-phase a.c. touching | |||||||||
Reference Method 1 &
11 (touching) |
Reference Method 1, 11
& 12 (in trefoil touching) |
Reference Method 1 & 11
(Flat touching) |
In
ducts |
In
ground |
In
ducts |
In
ground | ||||||||
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
| ||||||
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
| ||||||
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
| ||||||
50
|
0.98
|
0.99
|
0.21
|
1
|
0.86
|
0.18
|
0.87
|
0.84
|
0.25
|
0.88
|
1.10
|
0.99
|
0.93
|
0.86
|
70
|
0.67
|
0.68
|
0.20
|
0.71
|
0.59
|
0.17
|
0.62
|
0.6
|
0.25
|
0.65
|
0.80
|
0.70
|
0.70
|
0.61
|
95
|
0.49
|
0.51
|
0.195
|
0.55
|
0.44
|
0.17
|
0.47
|
0.46
|
0.24
|
0.52
|
0.65
|
0.53
|
0.56
|
0.46
|
120
|
0.39
|
0.41
|
0.190
|
0.45
|
0.35
|
0.165
|
0.39
|
0.38
|
0.24
|
0.44
|
0.55
|
0.43
|
0.48
|
0.37
|
150
|
0.31
|
0.33
|
0.185
|
0.38
|
0.29
|
0.160
|
0.33
|
0.31
|
0.23
|
0.39
|
0.50
|
0.37
|
0.43
|
0.32
|
185
|
0.25
|
0.27
|
0.185
|
0.33
|
0.23
|
0.160
|
0.28
|
0.26
|
0.23
|
0.34
|
0.45
|
0.31
|
0.39
|
0.27
|
240
|
0.195
|
0.21
|
0.180
|
0.28
|
0.18
|
0.155
|
0.24
|
0.21
|
0.22
|
0.30
|
0.40
|
0.26
|
0.35
|
0.23
|
300
|
0.155
|
0.17
|
0.175
|
0.25
|
0.145
|
0.150
|
0.21
|
0.17
|
0.22
|
0.28
|
0.37
|
0.24
|
0.32
|
0.21
|
400
|
0.115
|
0.145
|
0.170
|
0.22
|
0.125
|
0.150
|
0.195
|
0.160
|
0.21
|
0.27
|
0.35
|
0.21
|
0.30
|
0.19
|
500
|
0.093
|
0.125
|
0.170
|
0.21
|
0.105
|
0.145
|
0.180
|
0.145
|
0.20
|
0.25
|
0.33
|
0.20
|
0.28
|
0.18
|
630
|
0.073
|
0.105
|
0.165
|
0.195
|
0.092
|
0.145
|
0.170
|
0.135
|
0.195
|
0.24
|
0.30
|
0.19
|
0.26
|
0.17
|
800
|
0.056
|
0.090
|
0.160
|
0.190
|
0.086
|
0.140
|
0.165
|
0.130
|
0.180
|
0.23
|
0.28
|
0.18
|
0.24
|
0.16
|
1000
|
0.045
|
0.092
|
0.155
|
0.180
|
0.080
|
0.135
|
0.155
|
0.125
|
0.170
|
0.21
|
0.26
|
0.17
|
0.22
|
0.15
|
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
r = conductor resistance at operating temperature
x = reactance
z = impedance