APPLICATION |
This cable is mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
|
VOLTAGE RATING |
600/1000V
|
CONSTRUCTION |
Plain annealed copper, XLPE or XLEVA compound insulated, unarmoured or galvanized steel wires armoured, LSZH compound sheathed cable
|
INSULATION COLOUR |
|
SHEATH COLOUR |
Black or as per order
|
SPECIFICATION |
Refer BS6724, IEC60502-1, IEC60332-1, IEC60332-3, IEC60754, IEC61034
|
- Detailed Specification
- Current Rating and Voltage Drop
2-CORE
| ||||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| |||||||
Nominal Area
|
No./Dia of Strand
|
Thickness
|
Cable Overall Diameter
|
Approx. Weight
|
Cable Overall Diameter
|
Approx. Weight
| ||||
mm2
|
No./mm
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||
1.5
|
7/0.53
|
0.7
|
10.0
|
130
|
14.5
|
325
| ||||
2.5
|
7/0.67
|
0.7
|
11.0
|
165
|
15.5
|
400
| ||||
4
|
7/0.85
|
0.7
|
12.0
|
215
|
16.5
|
475
| ||||
6
|
7/1.04
|
0.7
|
13.0
|
270
|
18.0
|
570
| ||||
10
|
7/1.35
|
0.7
|
15.0
|
390
|
20.0
|
710
| ||||
16
|
7/1.70
|
0.7
|
17.0
|
550
|
22.0
|
1040
| ||||
25
|
7/2.14
|
0.9
|
20.4
|
670
|
26.0
|
1350
| ||||
35 (s)
|
19/1.53
|
0.9
|
22.7
|
880
|
23.5
|
1510
|
(s) : Sector Shaped Stranded Conductors
3-CORE
| ||||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| |||||||
Nominal Area
|
No./Dia of Strand
|
Thickness
|
Cable Overall Diameter
|
Approx. Weight
|
Cable Overall Diameter
|
Approx. Weight
| ||||
mm2
|
No./mm
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||
1.5
|
7/0.53
|
0.7
|
10.5
|
150
|
15.0
|
375
| ||||
2.5
|
7/0.67
|
0.7
|
11.4
|
195
|
16.0
|
400
| ||||
4
|
7/0.85
|
0.7
|
12.5
|
260
|
17.0
|
520
| ||||
6
|
7/1.04
|
0.7
|
14.0
|
320
|
18.0
|
640
| ||||
10
|
7/1.35
|
0.7
|
16.0
|
470
|
20.0
|
860
| ||||
16
|
7/1.70
|
0.7
|
18.0
|
680
|
23.0
|
1220
| ||||
25 (s)
|
12/1.70
|
0.9
|
19.8
|
950
|
24.8
|
1630
| ||||
35 (s)
|
19/1.53
|
0.9
|
21.5
|
1260
|
26.5
|
2050
| ||||
50 (s)
|
19/1.78
|
1.0
|
25.5
|
1670
|
30.5
|
2590
| ||||
70 (s)
|
19/.2.14
|
1.1
|
29.0
|
2340
|
35.8
|
3600
| ||||
95 (s)
|
19/2.52
|
1.1
|
32.0
|
3150
|
38.5
|
4590
| ||||
120 (s)
|
37/2.03
|
1.2
|
35.7
|
3930
|
42.5
|
5560
| ||||
150 (s)
|
37/2.25
|
1.4
|
40.5
|
4830
|
47.5
|
6920
| ||||
185 (s)
|
37/2.52
|
1.6
|
45.0
|
6050
|
52.0
|
8530
| ||||
240 (s)
|
61/2.25
|
1.7
|
53.5
|
8080
|
61.0
|
10900
| ||||
300 (s)
|
61/2.52
|
1.8
|
60.0
|
10070
|
68.0
|
13225
| ||||
400 (s)
|
61/2.85
|
2.0
|
65.5
|
12770
|
73.0
|
16200
|
(s) : Sector Shaped Stranded Conductors
4-CORE
| ||||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| |||||||
Nominal Area
|
No./Dia of Strand
|
Thickness
|
Cable Overall Diameter
|
Approx. Weight
|
Cable Overall Diameter
|
Approx. Weight
| ||||
mm2
|
No./mm
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||
1.5
|
7/0.53
|
0.7
|
11.5
|
180
|
15.5
|
410
| ||||
2.5
|
7/0.67
|
0.7
|
12.5
|
230
|
16.5
|
495
| ||||
4
|
7/0.85
|
0.7
|
14.0
|
315
|
18.0
|
610
| ||||
6
|
7/1.04
|
0.7
|
15.5
|
395
|
20.0
|
810
| ||||
10
|
1/1.35
|
0.7
|
17.5
|
590
|
22.7
|
1120
| ||||
16
|
7/1.70
|
0.7
|
20.0
|
860
|
26.0
|
1480
| ||||
25 (s)
|
12/1.70
|
0.9
|
21.5
|
1225
|
27.0
|
1980
| ||||
35 (s)
|
19/1.53
|
0.9
|
25.0
|
1625
|
30.4
|
2480
| ||||
50 (s)
|
19/1.78
|
1.0
|
28.0
|
2200
|
33.0
|
3180
| ||||
70 (s)
|
19/2.14
|
1.1
|
32.0
|
3050
|
38.5
|
4500
| ||||
95 (s)
|
19/2.52
|
1.1
|
37.0
|
4110
|
43.0
|
5775
| ||||
120 (s)
|
37/2.03
|
1.2
|
42.0
|
5915
|
49.0
|
7450
| ||||
150 (s)
|
37/2.25
|
1.4
|
46.0
|
6350
|
53.0
|
8830
| ||||
185 (s)
|
37/2.52
|
1.6
|
50.5
|
7985
|
58.0
|
10805
| ||||
240 (s)
|
61/2.25
|
1.7
|
58.0
|
10595
|
65.0
|
13630
| ||||
300 (s)
|
61/2.52
|
1.8
|
64.0
|
13220
|
71.5
|
16530
| ||||
400 (s)
|
61/2.85
|
2.0
|
73.0
|
16805
|
78.1
|
21840
|
(s) : Sector Shaped Stranded Conductors
Multi-Core Cables with XLPE (or LSZH) Insulation, PVC (or LSZH) Outsheath 300/500V or 600/1000V
Current-Carrying Capacities (Amp) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
Current-Carrying Capacities (Amp) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
Conductor Operating Temperature : 90°C | BS 7211 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor cross-sectional area
|
Reference Method 4 (enclosed in an conduit insulated wall etc)
|
Reference Method 3
(enclosed in conduit on a wall or ceiling, or in trunking) |
Reference Method 1 (clipped direct)
|
Reference Method 11
(on a perforated cable tray), or Reference Method 13 (free air) | |||
one 3-core cable or one 4-core cable 3-phase a.c.
|
one 2-core cable singlephase a.c. or d.c.
|
one 3-core cable or one 4-core cable 3-phase a.c.
|
one 2-core cable singlephase a.c. or d.c.
|
one 3-core cable or one 4-core cable 3-phase a.c.
|
one 2-core
cable singlephase a.c. or d.c. |
one 3-core
cable or one 4-core cable 3-phase a.c. | |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1.5
|
16.5
|
22
|
19.5
|
24
|
22
|
26
|
23
|
2.5
|
22
|
30
|
26
|
33
|
30
|
36
|
32
|
4
|
30
|
40
|
35
|
45
|
40
|
49
|
42
|
6
|
38
|
51
|
44
|
58
|
52
|
63
|
54
|
10
|
51
|
69
|
60
|
80
|
71
|
86
|
75
|
16
|
68
|
91
|
80
|
107
|
96
|
115
|
100
|
25
|
89
|
119
|
105
|
138
|
119
|
149
|
127
|
35
|
109
|
146
|
128
|
171
|
147
|
185
|
158
|
50
|
130
|
175
|
154
|
209
|
179
|
225
|
192
|
70
|
164
|
221
|
194
|
269
|
229
|
289
|
246
|
95
|
197
|
265
|
233
|
328
|
278
|
352
|
298
|
120
|
227
|
305
|
268
|
382
|
322
|
410
|
346
|
150
|
259
|
334
|
300
|
441
|
371
|
473
|
399
|
185
|
295
|
384
|
340
|
506
|
424
|
542
|
456
|
240
|
346
|
459
|
398
|
599
|
500
|
641
|
538
|
300
|
396
|
532
|
455
|
693
|
576
|
741
|
621
|
400
|
-
|
625
|
536
|
803
|
667
|
865
|
741
|
Voltage Drop (Per Amp Per Meter) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
Conductor Operating Temperature : 90°C | BS 7211 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor cross-sectional area
|
2-core cable d.c.
|
2-core cable single-phase a.c
|
3-core or 4-core cable 3-phase a.c.
| ||||
1
|
2
|
3
|
4
| ||||
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
| ||||
1.5
|
31
|
31
|
27
| ||||
2.5
|
19
|
19
|
16
| ||||
4
|
12
|
12
|
10
| ||||
6
|
7.9
|
7.9
|
6.8
| ||||
10
|
4.7
|
4.7
|
4.0
| ||||
16
|
2.9
|
2.9
|
2.5
| ||||
r
|
x
|
z
|
r
|
x
|
z
| ||
25
|
1.85
|
1.85
|
0.16
|
1.90
|
1.6
|
0.14
|
1.65
|
35
|
1.35
|
1.35
|
0.155
|
1.35
|
1.15
|
0.135
|
1.15
|
50
|
0.98
|
0.99
|
0.155
|
1.00
|
0.86
|
0.135
|
0.87
|
70
|
0.67
|
0.67
|
0.150
|
0.69
|
0.59
|
0.130
|
0.60
|
95
|
0.49
|
0.50
|
0.150
|
0.52
|
0.43
|
0.130
|
0.45
|
120
|
0.39
|
0.40
|
0.145
|
0.42
|
0.34
|
0.130
|
0.37
|
150
|
0.31
|
0.32
|
0.145
|
0.35
|
0.28
|
0.125
|
0.30
|
185
|
0.25
|
0.26
|
0.145
|
0.29
|
0.22
|
0.125
|
0.26
|
240
|
0.195
|
0.20
|
0.140
|
0.24
|
0.175
|
0.125
|
0.21
|
300
|
0.155
|
0.16
|
0.140
|
0.21
|
0.140
|
0.120
|
0.185
|
400
|
0.120
|
0.13
|
0.140
|
0.19
|
0.115
|
0.120
|
0.165
|
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
r = conductor resistance at operating temperature
x = reactance
z = impedance
Multi-Core Cables with XLPE (or LSZH) Insulation, Armoured, PVC or LSZH Outsheath 600/1000V
Current-Carrying Capacities (Amp) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables]
Current-Carrying Capacities (Amp) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables]
BS 6724 | |
Conductor Operating Temperature : 90°C | BS 7846 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor
cross-sectional area |
Reference Method 1 (clipped
direct) |
Reference Method 11 (on a
perforated horizontal cable tray or Reference Method 13 [free air] ) |
In single-way ducts
|
Laid direct in ground
| ||||
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
|
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
|
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
|
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
| |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1.5
|
27
|
23
|
29
|
25
|
-
|
23
|
-
|
28
|
2.5
|
36
|
31
|
39
|
33
|
-
|
30
|
-
|
36
|
4
|
49
|
42
|
52
|
44
|
-
|
40
|
-
|
48
|
6
|
62
|
53
|
66
|
56
|
-
|
50
|
-
|
60
|
10
|
85
|
73
|
90
|
78
|
-
|
65
|
-
|
80
|
16
|
110
|
94
|
115
|
99
|
115
|
94
|
140
|
115
|
25
|
146
|
124
|
152
|
131
|
145
|
125
|
180
|
150
|
35
|
180
|
154
|
188
|
162
|
175
|
150
|
215
|
180
|
50
|
219
|
187
|
228
|
197
|
210
|
175
|
255
|
215
|
70
|
279
|
238
|
291
|
251
|
260
|
215
|
315
|
265
|
95
|
338
|
289
|
354
|
304
|
310
|
260
|
380
|
315
|
120
|
392
|
335
|
410
|
353
|
355
|
300
|
430
|
360
|
150
|
451
|
386
|
472
|
406
|
400
|
335
|
480
|
405
|
185
|
515
|
441
|
539
|
463
|
455
|
380
|
540
|
460
|
240
|
607
|
520
|
636
|
546
|
520
|
440
|
630
|
530
|
300
|
698
|
599
|
732
|
628
|
590
|
495
|
700
|
590
|
400
|
787
|
673
|
847
|
728
|
660
|
560
|
790
|
670
|
Voltage Drop (Per Amp Per Meter) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables
BS 6724 | |
Conductor Operating Temperature : 90°C | BS 7846 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor
cross-sectional area |
2-core cable d.c.
|
2 cables, single-phase a.c.
|
3 or 4 cables, 3-phase a.c.
|
2 cables,
single-phase a.c. |
3 or 4 cables,
3-phase a.c. | ||||
In ducts or
in ground |
In ducts or
in ground | ||||||||
1
|
2
|
3
|
4
|
5
|
6
| ||||
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
| ||||
1.5
|
31.0
|
31.0
|
27.0
|
31.0
|
25.0
| ||||
2.5
|
19.0
|
19.0
|
16.0
|
19.0
|
15.0
| ||||
4
|
12.0
|
12.0
|
10.0
|
12.0
|
9.7
| ||||
6
|
7.9
|
7.9
|
6.8
|
7.9
|
6.5
| ||||
10
|
4.7
|
4.7
|
4.0
|
4.7
|
3.9
| ||||
16
|
2.9
|
2.9
|
2.5
|
2.9
|
2.6
| ||||
r
|
x
|
z
|
r
|
x
|
z
| ||||
25
|
1.850
|
1.350
|
0.160
|
1.900
|
1.600
|
0.140
|
1.650
|
1.900
|
1.600
|
35
|
1.350
|
1.350
|
0.155
|
1.350
|
1.150
|
0.135
|
1.150
|
1.350
|
1.200
|
50
|
0.980
|
0.990
|
0.155
|
1.000
|
0.860
|
0.135
|
0.870
|
1.000
|
0.870
|
70
|
0.670
|
0.670
|
0.150
|
0.690
|
0.590
|
0.130
|
0.600
|
0.690
|
0.610
|
95
|
0.490
|
0.500
|
0.150
|
0.520
|
0.430
|
0.130
|
0.450
|
0.520
|
0.450
|
120
|
0.390
|
0.400
|
0.145
|
0.420
|
0.340
|
0.130
|
0.370
|
0.420
|
0.360
|
150
|
0.310
|
0.320
|
0.145
|
0.350
|
0.280
|
0.125
|
0.300
|
0.350
|
0.300
|
185
|
0.250
|
0.260
|
0.145
|
0.290
|
0.220
|
0.125
|
0.260
|
0.290
|
0.250
|
240
|
0.195
|
0.200
|
0.140
|
0.240
|
0.175
|
0.125
|
0.210
|
0.240
|
0.210
|
300
|
0.155
|
0.160
|
0.140
|
0.210
|
0.140
|
0.120
|
0.185
|
0.210
|
0.190
|
400
|
0.120
|
0.130
|
0.140
|
0.190
|
0.115
|
0.120
|
0.165
|
0.190
|
0.180
|
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
r = conductor resistance at operating temperature
x = reactance
z = impedance