Low Voltage Cables
450 / 700V Single-Core
PVC Insulated, Non-Sheathed Cable
GROUNDING CABLE
APPLICATION |
This cable is used in light fitting, and in switching and control equipment. It can be installed in conduit, in cable trunking and on cable trays.
|
VOLTAGE RATING |
450/750V
|
CONSTRUCTION |
Plain annealed copper, PVC insulated cable
|
INSULATION COLOUR |
Brown, Black, Grey, Blue, Green/Yellow or as per order
|
SPECIFICATION |
SS358-3, BS6004, IEC60227-3
|
- Detailed Specification
- Current Rating and Voltage Drop
Conductor
|
Insulation
|
Approx. Diameter of Cable
|
Approx. Cable Weight
| ||||
Nominal Area
|
No./Dia of Strand
|
Approx. Diameter
|
Thickness
| ||||
mm2
|
No./mm
|
mm
|
mm
|
mm
|
kg/km
| ||
1.5
|
1/1.38
|
1.38
|
0.7
|
2.9
|
20
| ||
1.5
|
7/0.53
|
1.59
|
0.7
|
3.1
|
22
| ||
2.5
|
1/1.78
|
1.78
|
0.8
|
3.4
|
32
| ||
2.5
|
7/0.67
|
2.01
|
0.8
|
3.7
|
34
| ||
4
|
7/0.85
|
2.55
|
0.8
|
4.3
|
50
| ||
6
|
7/1.04
|
3.12
|
0.8
|
4.8
|
70
| ||
10
|
7/1.35
|
4.05
|
1.0
|
6.0
|
120
| ||
16
|
7/1.70
|
5.10
|
1.0
|
7.0
|
180
| ||
25
|
7/2.14
|
6.42
|
1.2
|
9.0
|
280
| ||
35
|
19/1.53
|
7.65
|
1.2
|
10.0
|
380
| ||
50
|
19/1.78
|
8.90
|
1.4
|
12.0
|
500
| ||
70
|
19/2.14
|
10.70
|
1.4
|
13.7
|
715
| ||
95
|
19/2.52
|
12.60
|
1.6
|
16.0
|
990
| ||
120
|
37/2.03
|
14.21
|
1.6
|
17.5
|
1220
| ||
150
|
37/2.25
|
15.75
|
1.8
|
19.5
|
1500
| ||
185
|
37/2.52
|
17.64
|
2.0
|
22.0
|
1890
| ||
240
|
61/2.25
|
20.25
|
2.2
|
25.0
|
2460
| ||
300
|
61/2.52
|
22.68
|
2.4
|
28.0
|
3080
| ||
400
|
61/2.85
|
25.65
|
2.6
|
31.5
|
3920
| ||
500
|
61/3.20
|
28.80
|
2.8
|
35.0
|
4920
| ||
630
|
127/2.52
|
32.76
|
2.8
|
39.0
|
6260
|
Single-Core Cables with PVC Insulation, Unarmoured, with or without Sheath 450/750V or 600/1000V
Current-Carrying Capacities (Amp) [ CU/PVC & CU/PVC/PVC Cables]
Current-Carrying Capacities (Amp) [ CU/PVC & CU/PVC/PVC Cables]
Low Voltage Cables
450 / 700V Single-Core
PVC Insulated, Non-Sheathed Cable (GROUNDING CABLE)
BS6004 | |
BS6346 | |
Conductor Operating Temperature : 70°C | SS358 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor cross-sectional area
|
Reference Method 4 (enclosed in conduit in thermally insulating wall etc.)
|
Reference Method 3 (enclosed in conduit on a wall or in trunking etc.)
|
Reference Method 1 (clipped direct)
|
Reference Method 11 (on a perforated cable tray horizontal or vertical)
|
Reference Method 12 (free air)
| ||||||
2 cables, single-phase a.c. or d.c.
|
3 or 4 cables, three phase a.c.
|
2 cables, single-phase a.c. or d.c.
|
3 or 4 cables, three-phase a.c.
|
2 cables, single-phase a.c. or d.c.flat and touching
|
3 or 4 cables, three-phase a.c. flat and touching or trefoil
|
2 cables, single-phase a.c.or d.c. or flat and touching
|
3 or 4 cable three -phase a.c. flat and touching or trefoil
|
2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c.
|
2 cables, single-phase a.c. or d.c. or 3 cables three phase a.c.
|
3 cables, trefoil three phase a.c.
| |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
BS 6004
| |||||||||||
1
|
11
|
10.5
|
13.5
|
12
|
15.5
|
14
|
-
|
-
|
-
|
-
|
-
|
1.5
|
14.5
|
13.5
|
17.5
|
15.5
|
20
|
18
|
-
|
-
|
-
|
-
|
-
|
2.5
|
19.5
|
18
|
24
|
21
|
27
|
25
|
-
|
-
|
-
|
-
|
-
|
4
|
26
|
24
|
32
|
28
|
37
|
33
|
-
|
-
|
-
|
-
|
-
|
6
|
34
|
31
|
41
|
36
|
47
|
43
|
-
|
-
|
-
|
-
|
-
|
10
|
46
|
42
|
57
|
50
|
65
|
59
|
-
|
-
|
-
|
-
|
-
|
16
|
61
|
56
|
76
|
68
|
87
|
79
| |||||
25
|
80
|
73
|
101
|
89
|
114
|
104
|
126
|
112
|
146
|
130
|
110
|
35
|
99
|
89
|
125
|
110
|
141
|
129
|
156
|
141
|
181
|
162
|
137
|
BS 6346
| |||||||||||
50
|
119
|
108
|
151
|
134
|
182
|
167
|
191
|
172
|
219
|
197
|
167
|
70
|
151
|
136
|
192
|
171
|
234
|
214
|
246
|
223
|
281
|
254
|
216
|
95
|
182
|
164
|
232
|
207
|
284
|
261
|
300
|
273
|
341
|
311
|
264
|
120
|
210
|
188
|
269
|
239
|
330
|
303
|
349
|
318
|
396
|
362
|
308
|
150
|
240
|
216
|
300
|
262
|
381
|
349
|
404
|
369
|
456
|
419
|
356
|
185
|
273
|
245
|
341
|
296
|
436
|
400
|
463
|
424
|
521
|
480
|
409
|
240
|
320
|
286
|
400
|
346
|
515
|
472
|
549
|
504
|
615
|
569
|
485
|
300
|
367
|
328
|
458
|
394
|
594
|
545
|
635
|
584
|
709
|
659
|
561
|
400
|
-
|
-
|
546
|
467
|
694
|
634
|
732
|
679
|
852
|
795
|
656
|
500
|
-
|
-
|
626
|
533
|
792
|
723
|
835
|
778
|
982
|
920
|
749
|
630
|
-
|
-
|
720
|
611
|
904
|
826
|
953
|
892
|
1138
|
1070
|
855
|
800
|
-
|
-
|
-
|
-
|
1030
|
943
|
1086
|
1020
|
1265
|
1188
|
971
|
1000
|
-
|
-
|
-
|
-
|
1154
|
1058
|
1216
|
1149
|
1420
|
1337
|
1079
|
Voltage Drop (Per Amp, Per Meter) [CU/PVC & CU/PVC/PVC Cables]
Low Voltage Cables
450 / 700V Single-Core
PVC Insulated, Non-Sheathed Cable (GROUNDING CABLE)
BS6004 | |
BS6346 | |
Conductor Operating Temperature : 70°C | SS358 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor
cross-sectional area |
2 cables
d.c. |
2 cables single-phase a.c.
|
3 or 4 cables three-phase a.c.
| |||||||||||||||||||
Ref. Methods 3 & 4 (enclosed in conduit etc, in or on a wall)
|
Ref. Methods 1 & 11 (clipped direct or on trays, touching)
|
Ref. Method 12 (space*)
|
Ref. Methods 3 & 4 (enclosed in conduit etc, in or on a wall)
|
Ref. Methods 1, 11 & 12 (in trefoil)
|
Ref. Methods 1 & 11 (Flat touching)
|
Ref. Method 12 (Flat spaced*)
| ||||||||||||||||
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
| ||||||||||||||
mm2
|
mV/A/m
| |||||||||||||||||||||
1
|
44
|
44
|
44
|
44
|
38
|
38
|
38
|
38
| ||||||||||||||
1.5
|
29
|
29
|
29
|
29
|
25
|
25
|
25
|
25
| ||||||||||||||
2.5
|
18
|
18
|
18
|
18
|
15
|
15
|
15
|
15
| ||||||||||||||
4
|
11
|
11
|
11
|
11
|
9.5
|
9.5
|
9.5
|
9.5
| ||||||||||||||
6
|
7.3
|
7.3
|
7.3
|
7.3
|
6.4
|
6.4
|
6.4
|
6.4
| ||||||||||||||
10
|
4.4
|
4.4
|
4.4
|
4.4
|
3.8
|
3.8
|
3.8
|
3.8
| ||||||||||||||
16
|
2.8
|
2.8
|
2.8
|
2.8
|
2.4
|
2.4
|
2.4
|
2.4
| ||||||||||||||
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
| ||
25
|
1.75
|
1.80
|
0.33
|
1.80
|
1.75
|
0.20
|
1.75
|
1.75
|
0.29
|
1.80
|
1.50
|
0.29
|
1.55
|
1.50
|
0.175
|
1.50
|
1.50
|
0.25
|
1.55
|
1.50
|
0.32
|
1.55
|
35
|
1.25
|
1.30
|
0.31
|
1.30
|
1.25
|
0.195
|
1.25
|
1.25
|
0.28
|
1.30
|
1.10
|
0.27
|
1.10
|
1.10
|
0.170
|
1.10
|
1.10
|
0.24
|
1.10
|
1.10
|
0.32
|
1.15
|
50
|
0.93
|
0.95
|
0.30
|
1.00
|
0.93
|
0.190
|
0.95
|
0.93
|
0.28
|
0.97
|
0.81
|
0.26
|
0.85
|
0.80
|
0.165
|
0.82
|
0.80
|
0.24
|
0.84
|
0.80
|
0.32
|
0.86
|
70
|
0.63
|
0.65
|
0.29
|
0.72
|
0.63
|
0.185
|
0.66
|
0.63
|
0.27
|
0.69
|
0.56
|
0.25
|
0.61
|
0.55
|
0.160
|
0.57
|
0.55
|
0.24
|
0.60
|
0.55
|
0.31
|
0.63
|
95
|
0.46
|
0.49
|
0.28
|
0.56
|
0.47
|
0.180
|
0.50
|
0.47
|
0.27
|
0.54
|
0.42
|
0.24
|
0.48
|
0.41
|
0.155
|
0.43
|
0.41
|
0.23
|
0.47
|
0.40
|
0.31
|
0.51
|
120
|
0.36
|
0.39
|
0.27
|
0.47
|
0.37
|
0.175
|
0.41
|
0.37
|
0.26
|
0.45
|
0.33
|
0.23
|
0.41
|
0.32
|
0.150
|
0.36
|
0.32
|
0.23
|
0.40
|
0.32
|
0.30
|
0.44
|
150
|
0.29
|
0.31
|
0.27
|
0.41
|
0.30
|
0.175
|
0.34
|
0.29
|
0.26
|
0.39
|
0.27
|
0.23
|
0.36
|
0.26
|
0.150
|
0.30
|
0.26
|
0.23
|
0.34
|
0.26
|
0.30
|
0.40
|
185
|
0.23
|
0.25
|
0.27
|
0.37
|
0.24
|
0.170
|
0.29
|
0.24
|
0.26
|
0.35
|
0.22
|
0.23
|
0.32
|
0.21
|
0.145
|
0.26
|
0.21
|
0.22
|
0.31
|
0.21
|
0.30
|
0.36
|
240
|
0.180
|
0.195
|
0.26
|
0.33
|
0.185
|
0.165
|
0.25
|
0.185
|
0.25
|
0.31
|
0.17
|
0.23
|
0.29
|
0.160
|
0.145
|
0.22
|
0.160
|
0.22
|
0.27
|
0.160
|
0.29
|
0.34
|
300
|
0.145
|
0.160
|
0.26
|
0.31
|
0.150
|
0.165
|
0.22
|
0.150
|
0.25
|
0.29
|
0.14
|
0.23
|
0.27
|
0.130
|
0.140
|
0.190
|
0.130
|
0.22
|
0.25
|
0.130
|
0.29
|
0.32
|
400
|
0.105
|
0.130
|
0.26
|
0.29
|
0.120
|
0.160
|
0.20
|
0.115
|
0.25
|
0.27
|
0.12
|
0.22
|
0.25
|
0.105
|
0.140
|
0.175
|
0.105
|
0.21
|
0.24
|
0.100
|
0.29
|
0.31
|
500
|
0.086
|
0.110
|
0.26
|
0.28
|
0.098
|
0.155
|
0.185
|
0.093
|
0.24
|
0.26
|
0.10
|
0.22
|
0.25
|
0.086
|
0.135
|
0.160
|
0.086
|
0.21
|
0.23
|
0.081
|
0.29
|
0.30
|
630
|
0.068
|
0.094
|
0.25
|
0.27
|
0.081
|
0.155
|
0.175
|
0.076
|
0.24
|
0.25
|
0.08
|
0.22
|
0.24
|
0.072
|
0.135
|
0.150
|
0.072
|
0.21
|
0.22
|
0.066
|
0.28
|
0.29
|
800
|
0.053
|
-
|
-
|
-
|
0.068
|
0.150
|
0.165
|
0.061
|
0.24
|
0.25
|
-
|
-
|
-
|
0.060
|
0.130
|
0.145
|
0.060
|
0.21
|
0.22
|
0.053
|
0.28
|
0.29
|
1000
|
0.042
|
-
|
-
|
-
|
0.059
|
0.150
|
0.160
|
0.050
|
0.24
|
0.24
|
-
|
-
|
-
|
0.052
|
0.130
|
0.140
|
0.052
|
0.20
|
0.21
|
0.044
|
0.28
|
0.28
|
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
r = conductor resistance at operating temperature
x = reactance
z = impedance