Low Voltage Cables
600 / 1000V 2-Core ~ 4-Core
XLPE Insulated, Unarmoured & Armoured
PVC Sheathed Cable
APPLICATION |
This cable is primarily used for main power supply. It can be installed in cable ducts, in cable trunking, on cable trays, and on cable ladders.
|
VOLTAGE RATING |
600/1000V
|
CONSTRUCTION |
Plain annealed copper, XLPE insulated, unarmoured or galvanized steel wires armoured, PVC sheathed cable
|
INSULATION COLOUR |
|
SHEATH COLOUR |
Black
|
SPECIFICATION |
IEC60502-1
|
- Detailed Specification
- Current Rating and Voltage Drop
2-CORE
| |||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| ||||||
Nominal Area
|
Thickness
|
Approx. Overall Diameter
|
Approx. Cable Weight
|
Approx. Overall Diameter
|
Approx. Cable Weight
| ||||
mm2
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||
1.5 (cs)
|
0.7
|
10.1
|
130
|
14.0
|
350
| ||||
2.5 (cs)
|
0.7
|
11.0
|
160
|
14.8
|
410
| ||||
4 (cs)
|
0.7
|
12.0
|
200
|
16.6
|
490
| ||||
6 (cs)
|
0.7
|
13.1
|
260
|
17.5
|
580
| ||||
10 (cs)
|
0.7
|
15.0
|
380
|
19.5
|
800
| ||||
16 (cs)
|
0.7
|
17.2
|
530
|
22.5
|
1050
| ||||
25 (s)
|
0.9
|
17.0
|
660
|
21.5
|
1270
| ||||
35 (s)
|
0.9
|
18.5
|
870
|
24.5
|
1530
| ||||
50 (s)
|
1.0
|
21.0
|
1140
|
26.0
|
1870
| ||||
70 (s)
|
1.1
|
23.5
|
1570
|
29.5
|
2400
| ||||
95 (s)
|
1.1
|
26.5
|
2120
|
33.5
|
3350
| ||||
120 (s)
|
1.2
|
29.5
|
2640
|
36.5
|
4000
| ||||
150 (s)
|
1.4
|
33.0
|
3250
|
39.5
|
4700
| ||||
185 (s)
|
1.6
|
36.5
|
4050
|
44.5
|
6200
| ||||
240 (s)
|
1.7
|
46.0
|
5300
|
53.0
|
7700
| ||||
300 (s)
|
1.8
|
50.0
|
6590
|
58.0
|
9400
| ||||
400 (s)
|
2.0
|
54.0
|
8370
|
62.0
|
11500
|
(cs) : Circular Stranded
(s) : Sector Shaped Stranded Conductors
(s) : Sector Shaped Stranded Conductors
3-CORE
| |||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| ||||||
Nominal Area
|
Thickness
|
Approx. Overall Diameter
|
Approx. Cable Weight
|
Approx. Overall Diameter
|
Approx. Cable Weight
| ||||
mm2
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||
1.5 (cs)
|
0.7
|
10.5
|
145
|
14.5
|
390
| ||||
2.5 (cs)
|
0.7
|
11.3
|
190
|
15.5
|
435
| ||||
4 (cs)
|
0.7
|
12.8
|
250
|
17.0
|
550
| ||||
6 (cs)
|
0.7
|
13.9
|
320
|
18.5
|
660
| ||||
10 (cs)
|
0.7
|
15.9
|
480
|
20.4
|
900
| ||||
16 (cs)
|
0.7
|
18.1
|
700
|
23.4
|
1260
| ||||
25 (s)
|
0.9
|
20.0
|
920
|
25.0
|
1630
| ||||
35 (s)
|
0.9
|
22.0
|
1200
|
27.0
|
2000
| ||||
50 (s)
|
1.0
|
26.0
|
1660
|
30.5
|
2500
| ||||
70 (s)
|
1.1
|
28.0
|
2230
|
35.0
|
3600
| ||||
95 (s)
|
1.1
|
32.0
|
3100
|
38.5
|
4600
| ||||
120 (s)
|
1.2
|
35.5
|
3850
|
42.0
|
5500
| ||||
150 (s)
|
1.4
|
40.0
|
4830
|
47.5
|
7000
| ||||
185 (s)
|
1.6
|
44.0
|
6000
|
52.0
|
8460
| ||||
240 (s)
|
1.7
|
53.5
|
7800
|
62.0
|
10550
| ||||
300 (s)
|
1.8
|
60.0
|
9880
|
68.5
|
12530
| ||||
400 (s)
|
2.0
|
65.5
|
12200
|
74.0
|
22200
|
(cs) : Circular Stranded
(s) : Sector Shaped Stranded Conductors
(s) : Sector Shaped Stranded Conductors
4-CORE
| |||||||||
Conductor
|
Insulation
|
Unarmoured Cable
|
Armoured Cable
| ||||||
Nominal Area
|
Thickness
|
Approx. Overall Diameter
|
Approx. Cable Weight
|
Approx. Overall Diameter
|
Approx. Cable Weight
| ||||
mm2
|
mm
|
mm
|
kg/km
|
mm
|
kg/km
| ||||
1.5 (cs)
|
0.7
|
11.3
|
170
|
15.3
|
430
| ||||
2.5 (cs)
|
0.7
|
12.3
|
225
|
17.0
|
520
| ||||
4 (cs)
|
0.7
|
13.8
|
300
|
18.5
|
640
| ||||
6 (cs)
|
0.7
|
15.2
|
390
|
19.8
|
740
| ||||
10 (cs)
|
0.7
|
17.5
|
580
|
23.0
|
1030
| ||||
16 (cs)
|
0.7
|
20.0
|
840
|
26.0
|
1650
| ||||
25 (s)
|
0.9
|
22.0
|
1200
|
27.5
|
2000
| ||||
35 (s)
|
0.9
|
25.5
|
1600
|
30.5
|
2500
| ||||
50 (s)
|
1.0
|
27.5
|
2100
|
33.5
|
3100
| ||||
70 (s)
|
1.1
|
34.0
|
3000
|
38.5
|
4500
| ||||
95 (s)
|
1.1
|
36.5
|
4100
|
43.0
|
5700
| ||||
120 (s)
|
1.2
|
41.0
|
5160
|
49.0
|
7460
| ||||
150 (s)
|
1.4
|
46.5
|
6300
|
53.0
|
8800
| ||||
185 (s)
|
1.6
|
51.5
|
8000
|
59.0
|
10800
| ||||
240 (s)
|
1.7
|
58.5
|
10500
|
68.0
|
13600
| ||||
300 (s)
|
1.8
|
64.0
|
13100
|
73.0
|
16200
| ||||
400 (s)
|
2.0
|
73.0
|
16700
|
83.0
|
22200
|
(cs) : Circular Stranded
(s) : Sector Shaped Stranded Conductors
(s) : Sector Shaped Stranded Conductors
Multi-Core Cables with XLPE (or LSZH) Insulation, PVC (or LSZH) Outsheath 300/500V or 600/1000V
Current-Carrying Capacities (Amp) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
Current-Carrying Capacities (Amp) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
Conductor Operating Temperature : 90°C | BS 7211 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor cross-sectional area
|
Reference Method 4 (enclosed in an conduit insulated wall etc)
|
Reference Method 3
(enclosed in conduit on a wall or ceiling, or in trunking) |
Reference Method 1 (clipped direct)
|
Reference Method 11
(on a perforated cable tray), or Reference Method 13 (free air) | |||
one 3-core cable or one 4-core cable 3-phase a.c.
|
one 2-core cable singlephase a.c. or d.c.
|
one 3-core cable or one 4-core cable 3-phase a.c.
|
one 2-core cable singlephase a.c. or d.c.
|
one 3-core cable or one 4-core cable 3-phase a.c.
|
one 2-core
cable singlephase a.c. or d.c. |
one 3-core
cable or one 4-core cable 3-phase a.c. | |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1.5
|
16.5
|
22
|
19.5
|
24
|
22
|
26
|
23
|
2.5
|
22
|
30
|
26
|
33
|
30
|
36
|
32
|
4
|
30
|
40
|
35
|
45
|
40
|
49
|
42
|
6
|
38
|
51
|
44
|
58
|
52
|
63
|
54
|
10
|
51
|
69
|
60
|
80
|
71
|
86
|
75
|
16
|
68
|
91
|
80
|
107
|
96
|
115
|
100
|
25
|
89
|
119
|
105
|
138
|
119
|
149
|
127
|
35
|
109
|
146
|
128
|
171
|
147
|
185
|
158
|
50
|
130
|
175
|
154
|
209
|
179
|
225
|
192
|
70
|
164
|
221
|
194
|
269
|
229
|
289
|
246
|
95
|
197
|
265
|
233
|
328
|
278
|
352
|
298
|
120
|
227
|
305
|
268
|
382
|
322
|
410
|
346
|
150
|
259
|
334
|
300
|
441
|
371
|
473
|
399
|
185
|
295
|
384
|
340
|
506
|
424
|
542
|
456
|
240
|
346
|
459
|
398
|
599
|
500
|
641
|
538
|
300
|
396
|
532
|
455
|
693
|
576
|
741
|
621
|
400
|
-
|
625
|
536
|
803
|
667
|
865
|
741
|
Voltage Drop (Per Amp Per Meter) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
Conductor Operating Temperature : 90°C | BS 7211 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor cross-sectional area
|
2-core cable d.c.
|
2-core cable single-phase a.c
|
3-core or 4-core cable 3-phase a.c.
| ||||
1
|
2
|
3
|
4
| ||||
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
| ||||
1.5
|
31
|
31
|
27
| ||||
2.5
|
19
|
19
|
16
| ||||
4
|
12
|
12
|
10
| ||||
6
|
7.9
|
7.9
|
6.8
| ||||
10
|
4.7
|
4.7
|
4.0
| ||||
16
|
2.9
|
2.9
|
2.5
| ||||
r
|
x
|
z
|
r
|
x
|
z
| ||
25
|
1.85
|
1.85
|
0.16
|
1.90
|
1.6
|
0.14
|
1.65
|
35
|
1.35
|
1.35
|
0.155
|
1.35
|
1.15
|
0.135
|
1.15
|
50
|
0.98
|
0.99
|
0.155
|
1.00
|
0.86
|
0.135
|
0.87
|
70
|
0.67
|
0.67
|
0.150
|
0.69
|
0.59
|
0.130
|
0.60
|
95
|
0.49
|
0.50
|
0.150
|
0.52
|
0.43
|
0.130
|
0.45
|
120
|
0.39
|
0.40
|
0.145
|
0.42
|
0.34
|
0.130
|
0.37
|
150
|
0.31
|
0.32
|
0.145
|
0.35
|
0.28
|
0.125
|
0.30
|
185
|
0.25
|
0.26
|
0.145
|
0.29
|
0.22
|
0.125
|
0.26
|
240
|
0.195
|
0.20
|
0.140
|
0.24
|
0.175
|
0.125
|
0.21
|
300
|
0.155
|
0.16
|
0.140
|
0.21
|
0.140
|
0.120
|
0.185
|
400
|
0.120
|
0.13
|
0.140
|
0.19
|
0.115
|
0.120
|
0.165
|
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
r = conductor resistance at operating temperature
x = reactance
z = impedance
Multi-Core Cables with XLPE (or LSZH) Insulation, Armoured, PVC or LSZH Outsheath 600/1000V
Current-Carrying Capacities (Amp) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables]
Current-Carrying Capacities (Amp) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables]
BS 6724 | |
Conductor Operating Temperature : 90°C | BS 7846 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor
cross-sectional area |
Reference Method 1 (clipped
direct) |
Reference Method 11 (on a
perforated horizontal cable tray or Reference Method 13 [free air] ) |
In single-way ducts
|
Laid direct in ground
| ||||
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
|
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
|
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
|
one 2-core cable single phase a.c. or d.c.
|
one 3-core or 4-core cable 3-phase a.c.
| |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1.5
|
27
|
23
|
29
|
25
|
-
|
23
|
-
|
28
|
2.5
|
36
|
31
|
39
|
33
|
-
|
30
|
-
|
36
|
4
|
49
|
42
|
52
|
44
|
-
|
40
|
-
|
48
|
6
|
62
|
53
|
66
|
56
|
-
|
50
|
-
|
60
|
10
|
85
|
73
|
90
|
78
|
-
|
65
|
-
|
80
|
16
|
110
|
94
|
115
|
99
|
115
|
94
|
140
|
115
|
25
|
146
|
124
|
152
|
131
|
145
|
125
|
180
|
150
|
35
|
180
|
154
|
188
|
162
|
175
|
150
|
215
|
180
|
50
|
219
|
187
|
228
|
197
|
210
|
175
|
255
|
215
|
70
|
279
|
238
|
291
|
251
|
260
|
215
|
315
|
265
|
95
|
338
|
289
|
354
|
304
|
310
|
260
|
380
|
315
|
120
|
392
|
335
|
410
|
353
|
355
|
300
|
430
|
360
|
150
|
451
|
386
|
472
|
406
|
400
|
335
|
480
|
405
|
185
|
515
|
441
|
539
|
463
|
455
|
380
|
540
|
460
|
240
|
607
|
520
|
636
|
546
|
520
|
440
|
630
|
530
|
300
|
698
|
599
|
732
|
628
|
590
|
495
|
700
|
590
|
400
|
787
|
673
|
847
|
728
|
660
|
560
|
790
|
670
|
Voltage Drop (Per Amp Per Meter) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables
BS 6724 | |
Conductor Operating Temperature : 90°C | BS 7846 |
Ambient Temperature : 30°C | IEC60502-1 |
Conductor
cross-sectional area |
2-core cable d.c.
|
2 cables, single-phase a.c.
|
3 or 4 cables, 3-phase a.c.
|
2 cables,
single-phase a.c. |
3 or 4 cables,
3-phase a.c. | ||||
In ducts or
in ground |
In ducts or
in ground | ||||||||
1
|
2
|
3
|
4
|
5
|
6
| ||||
mm2
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
|
mV/A/m
| ||||
1.5
|
31.0
|
31.0
|
27.0
|
31.0
|
25.0
| ||||
2.5
|
19.0
|
19.0
|
16.0
|
19.0
|
15.0
| ||||
4
|
12.0
|
12.0
|
10.0
|
12.0
|
9.7
| ||||
6
|
7.9
|
7.9
|
6.8
|
7.9
|
6.5
| ||||
10
|
4.7
|
4.7
|
4.0
|
4.7
|
3.9
| ||||
16
|
2.9
|
2.9
|
2.5
|
2.9
|
2.6
| ||||
r
|
x
|
z
|
r
|
x
|
z
| ||||
25
|
1.850
|
1.350
|
0.160
|
1.900
|
1.600
|
0.140
|
1.650
|
1.900
|
1.600
|
35
|
1.350
|
1.350
|
0.155
|
1.350
|
1.150
|
0.135
|
1.150
|
1.350
|
1.200
|
50
|
0.980
|
0.990
|
0.155
|
1.000
|
0.860
|
0.135
|
0.870
|
1.000
|
0.870
|
70
|
0.670
|
0.670
|
0.150
|
0.690
|
0.590
|
0.130
|
0.600
|
0.690
|
0.610
|
95
|
0.490
|
0.500
|
0.150
|
0.520
|
0.430
|
0.130
|
0.450
|
0.520
|
0.450
|
120
|
0.390
|
0.400
|
0.145
|
0.420
|
0.340
|
0.130
|
0.370
|
0.420
|
0.360
|
150
|
0.310
|
0.320
|
0.145
|
0.350
|
0.280
|
0.125
|
0.300
|
0.350
|
0.300
|
185
|
0.250
|
0.260
|
0.145
|
0.290
|
0.220
|
0.125
|
0.260
|
0.290
|
0.250
|
240
|
0.195
|
0.200
|
0.140
|
0.240
|
0.175
|
0.125
|
0.210
|
0.240
|
0.210
|
300
|
0.155
|
0.160
|
0.140
|
0.210
|
0.140
|
0.120
|
0.185
|
0.210
|
0.190
|
400
|
0.120
|
0.130
|
0.140
|
0.190
|
0.115
|
0.120
|
0.165
|
0.190
|
0.180
|
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
r = conductor resistance at operating temperature
x = reactance
z = impedance