Branch Circuit | The part of a distribution system consisting of circuit conductors, between the final overcurrent protection and the outlet or load attached. |
Busbar | Thick, rigid strips or bars of copper that serve as a common connection between several circuits. Busbars are usually used near the switchboard and can be enclosed in busways. |
Busway | The part of a distribution system consisting of metal enclosed busbars. Busways come in premade sections that can be fitted to any shape needed. |
Center Tap | The point where all three windings are connected to each other in a wye connection. For delta connections, one of the lines must be tapped to produce a neutral. |
Copper Loss | A power loss due to current flowing through wire. Copper loss is proportional to the resistance of the wire and the square of the current. |
Core | A component of a transformer. The iron or steel core provides a controlled path for the magnetic flux generated in the transformer by the current flowing through the windings. |
Delta | A connection of three components where a triangular series circuit is formed. Delta connections are used in three phase power systems. |
Delta/Delta | A transformer with both the primary and the secondary connected as a delta. |
Delta/Wye | A transformer with the primary connected as a delta and the secondary connected as a wye. |
Distribution Substation | A bank of step-down transformers near the end users. The distribution substation converts voltage closer to the required usable levels. |
Distribution System | A circuit of users linked to a generating station and substations that is typically arranged in either a radial or interconnected manner. Local distribution systems transport power within a building. |
Enclosure | A physical barrier designed to provide mechanical or electrical protection for components used in a system. |
Feeder | A circuit conductor between the power supply source and a final branch circuit overcurrent device. |
Generating Station | A building where a utility company houses large linked AC generators to create the massive power for widespread use. |
Grounded Conductor | A system conductor that is intentionally grounded. |
Grounding Conductor | A conductor used to connect equipment in a wiring system to ground. |
Interconnected System | A distribution system with multiple available power sources that can loop throughout the network. If one source goes down, a different source can be activated to maintain service. |
Kilovolt-Amp | A unit used to rate transformer and generator strength. A kilovolt is a thousand volts. |
Laminated | Sealed together in multiple layers of thin sheets to construct the core for a transformer. Lamination helps reduce resistance losses. |
Line Voltage | The voltage present between any two of the conductors in a three-phase system. It is 1.732 times higher than phase voltage in a wye connection. |
Load Center | A device found in residential locations that performs the same functions as a panelboard does in commercial settings. Load centers are not required to have many panelboard safety features because homes do not draw the same amount of current as industry. |
Local Power Distribution System | The part of a distribution system located within a building. Local distribution systems are the responsibility of shop electricians and maintenance workers and fall under NEC rules. |
Main Disconnect Switch | A heavy, spring-loaded switch on a factory switchboard that can cut off power to the entire building. Switchboards with more than six switches or breakers are required by the NEC to have a main disconnect. |
Motor Control Center | A modular assembly specifically designed to plug in motor control units. Motor control centers are supplied by a common bus, usually straight from the switchboard. |
Mutual Induction | The ability of one coil to induce a voltage into another coil. This principle is used in transformers to step up or step down voltage. |
NEC | The standard for minimum safe electrical installations. The National Electrical Code is adopted in some form as law in all 50 states. |
Network System | A distribution system where multiple power sources are connected to each user to guarantee uninterrupted power. A network system is expensive, so it is used only when constant power is vital. |
Open Delta | A transformer connection that does not complete the triangle, using only two of the three sides. An open delta is used when full power is not needed. |
Overcurrent | Excess current that may result from overload, short circuit, or ground fault. Devices like fuses and circuit breakers protect against overcurrent. |
Panelboard | A single panel distribution cabinet or wall cutout box that holds automatic overcurrent protection devices for lighting, heat, or power circuits. |
Phase Symbol | (Φ) The Greek letter Phi, used to represent phases, such as in a 3Φ4W system. |
Phase Voltage | The voltage between any one conductor and ground. |
Plug-In Busway | A type of feeder busway with electrical control that allows loads to be added along the bus structure. |
Primary Winding | Turns of wire on a transformer core, used to transfer voltage from the input to the core. |
Radial System | A distribution system with only one power source. If that source goes out, power is lost to the entire circuit. |
Revolving Field Generator | A generator setup where an electromagnetic field is rotated between the conductor wound armature. Most AC generators are of this design. |
Secondary Winding | Turns of wire on a transformer core, used to transfer voltage from the core to the outside load. |
Service-Entrance | The point where electricity enters a buidling. A service-entrance switchboard has metering equipment and devices for overcurrent protection and electrical control. |
Single-Phase | A continuous single alternating current cycle. |
Step Up | In electricity, a phrase used to describe voltage adjustment. To step up voltage means to increase voltage. |
Substation | Any grouping of switchgear and transformers located near a source or user. Substations are used to alter voltage levels and provide a service point of electrical control. |
Switchboard | A freestanding assembly of panels with metering equipment, overcurrent and other protection devices. Switchboards take a large block of power from a substation and break it down into smaller blocks for use within a building. |
Switchgear | A combination of disconnect switches and breakers used to isolate equipment in substations. |
Tap | A wire connected to the midpoint of a transformer secondary winding. This allows the transformer to use different turns ratios. |
Terminal | A connecting point in a circuit where a wire is attached to create an electrical connection. |
Three-Phase | A continuous series of three overlapping AC cycles offset by 120 degrees. Three-phase power is used for all large scale distribution systems. |
Three-Phase Power | The most common form of AC power for distribution. Three-phase power has three overlapping AC cycles offset by 120 degrees. |
Transformer | A device that transfers electrical energy from one circuit to another, without changing the frequency, using electromagnetic induction. A transformer is most often used to change the line voltage. |
Transmission Substation | A bank of step up transformers near the generating station. Transmission substations increase voltage as high as 800kV for widespread distribution. |
Turns Ratio | A comparison of the number of turns in the primary versus the number of turns in the secondary of a transformer. |
Wye | A connection of three components where one end of each component is connected at a common point. Wye connections are used in three phase power systems. |
Wye/Delta | A transformer with the primary connected as a wye and the secondary connected as a delta. |
Wye/Wye | A transformer with both the primary and the secondary connected as a wye.
|
No comments:
Post a Comment