Results 1 to 14 of 14
  1. #1
    bestbowl is offlineMember
    Join Date
    Apr 2007
    Posts
    31

    Question What is the difference between THWN & THHN wire?

    Just wondering what is the difference and what is better for my different applications.
    Thanks.
  2. Sponsored Links
  3. #2
    ray2047's Avatar
    ray2047 is online nowGroup Moderator
    Join Date
    Mar 2006
    State:
    TX
    Posts
    16,469
    W indicates sutiable for use in wet locations.
  4. #3
    nap's Avatar
    nap 
    nap is offlineNew Member
    Join Date
    May 2006
    Posts
    4,291
    most thhn wire is dual rated as thwn.

    check to be sure the wire you purchase is so.
  5. #4
    ddr 
    ddr is offlineMember
    Join Date
    May 2006
    State:
    NY
    Posts
    134
    THHN is a code for heat-resistant thermoplastic wire which is allowed for use in dry to damp locations and rated for a maximum temperature of 90ºC (194ºF).

    THWN is a code for heat- and moisture-resistant thermoplastic wire which is allowed for use in both dry and wet locations but has a lower maximum temperature rating of 75ºC (167ºF).

    As nap said, wire can be dual rated (THHN/THWN). Be careful not to misread the code as there are similar ones for different type wires (such as THHW) while others have suffixes (such as -2) which change the wire’s rating.
  6. #5
    bestbowl is offlineMember
    Join Date
    Apr 2007
    Posts
    31

    So if the wire is dual rated thhn thwn is it usually 75C or 90C and/or is it

    the temperature usually also indicated on the wire?
  7. #6
    nap's Avatar
    nap 
    nap is offlineNew Member
    Join Date
    May 2006
    Posts
    4,291
    I don't recall seeing a temp rating on the wire I generally use although it could be. Never really paid that much attention to it. I'll have to take a look.

    The temp rating I have is within the NEC.
  8. #7
    jwhite is offlineMember
    Join Date
    Apr 2006
    Posts
    1,644
    "So if the wire is dual rated thhn thwn is it usually 75C or 90C and/or is it "

    If the wire is duel rated it can be used at 75 c if used in a wet location or 90 if used in a dry location.

    THHN/THWN-2 can be used at the 90 deg rating in a wet or dry location.

    Keep in mind that the 90 deg columb is rarely if ever the final amp rating for a given wire size. In DIY work, it will likely never be the final amp rating of the wire. The purpose of the 90 deg columb is for a starting point when doing bundling, ambient temp, etc calculations. 

    If running conduit and individual conductors, most of the time the limit will be the 75 deg columb, as the lugs on the equipment will only have a 75 deg rating.

    If running NM or NMB cable (romex) the limit will be the 60 deg columb, regardless of the wire type.
  9. #8
    ray2047's Avatar
    ray2047 is online nowGroup Moderator
    Join Date
    Mar 2006
    State:
    TX
    Posts
    16,469
    Apologies in advance for slightly hijacking this thread but is dual rated acceptable for over head (in air) use to supply power to another structure? (Four # 10 suppling a 30 amp sub panel for example.)
  10. #9
    jwhite is offlineMember
    Join Date
    Apr 2006
    Posts
    1,644
    duel rated just means rated for more than one thing. If the wire is duel rated for thhn/thwn, then no not for overhead wiring. If the wire is duel rated for overhead and something else then yes.
  11. #10
    ibpooks is offlineMember
    Join Date
    Feb 2005
    State:
    MI
    Posts
    7,821
    Ray,

    Overhead wiring must carry a UV/sunlight exposure rating which THHN/THWN does not have.

    Overhead wires must also be supported by a load-bearing messenger wire which is only included in the triplex/quadplex cable assemblies that are sold for overhead services.
  12. #11
    ray2047's Avatar
    ray2047 is online nowGroup Moderator
    Join Date
    Mar 2006
    State:
    TX
    Posts
    16,469
    ibpooks, thanks for figuring out my somewhat unclear post. (I left out THHN/THWN). So I'm assuming the way I learned with individual conductors fastened to individual insulators is no longer permitted.

    I assume if you were running to a garage with other metallic pathways you'd need a four wire cable assembly. I doubt fourplex even exist when you get down as small as #10, correct? Dang, didn't want to go the burial route.
  13. #12
    ibpooks is offlineMember
    Join Date
    Feb 2005
    State:
    MI
    Posts
    7,821
    > I assume if you were running to a garage with other metallic pathways
    > you'd need a four wire cable assembly.

    Yes. It's highly recommended anyway.

    > I doubt fourplex even exist when you get down as small as #10, correct?

    The smallest I've seen is #2 aluminum which is rated for 100A as a dwelling feeder. In any case, I hardly ever recommend feeding an outbuilding with anything less than #2 aluminum.

    If you really want a smaller feeder, I know the power company uses #4 aluminum, so you might be able to get your hands on that somewhere.
  14. #13
    ray2047's Avatar
    ray2047 is online nowGroup Moderator
    Join Date
    Mar 2006
    State:
    TX
    Posts
    16,469
    Thanks all. Guess I'll have to dig.
  15. #14
    jwhite is offlineMember
    Join Date
    Apr 2006
    Posts
    1,644